Skip to main content
Schneider Electric A9F45402 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F45402 Acti9 iC60N MCB, D Curve, 2 A, 4

MPNA9F45402
Obsolete

Schneider Electric Acti9 iC60N, A9F45402, miniature circuit breaker, 4P, D curve, 2 A, 50 kA breaking capacity, clip-on rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F45402 — Identification
ParameterValue
Product nameDisbo iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
A9F45402 — Ratings
ParameterValue
Rated current (In)2 A
Poles configuration4P
Number of protected poles4
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated operational voltage (Ue)12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
A9F45402 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F45402 — Mechanical
ParameterValue
Mounting supportRail
Mounting modeClip-on
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height85 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F45402 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F45402 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2

Product details

The A9F45402 is a 4-pole Acti9 iC60N miniature circuit breaker rated 2 A with a D curve, meaning the magnetic trip operates at 12 x In (24 A) plus or minus 20%. The thermal-magnetic trip unit handles the overload side; the magnetic element clears short-circuits. Dual-rated to EN/IEC 60898-1 and EN/IEC 60947-2, so it qualifies for both domestic-distribution and industrial panel applications.

Depth 78.5 mm, height 85 mm. The 4-pole form factor with a single neutral and three protected poles means it fits a 4-wire three-phase distribution board. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible, stripped to 14 mm, torqued to 2 N·m. IP20 finger-safe front; padlockable for lockout-tagout. The white housing with a toggle actuator and trip indicator is standard Acti9 family appearance.

D curve selection logic

The D curve (12 x In magnetic trip) distinguishes this from the more common B (3–5 x In) or C (5–10 x In) variants in the same iC60N family. For a 2 A rating, the D curve holds through a 24 A peak before the magnetic element fires — that is the deciding factor for transformer primary protection or contactor coil circuits where the inrush lasts several cycles. If the load is resistive or general-purpose with no high inrush, a C curve would trip faster on fault; but for motorized or inductive loads, D is the correct call.

Frequently asked questions

How do I get pricing and availability for A9F45402?

Submit an RFQ through the storefront. The part is sourced to order through independent distribution; current pricing and stock are confirmed at quote time.

What is the closest alternative to A9F45402 in the Acti9 family?

Within the same iC60N platform, the only difference between order codes is the curve (B/C/D), poles (1P–4P), and rated current. A 2 A C-curve 4P (A9F45401) is the same physical footprint and breaking capacity, but trips at 5–10 x In instead of 12 x In. Choose the curve based on the load's inrush profile.

What is the depth of A9F45402?

The depth is 78.5 mm, with a width of 72 mm (8 x 9 mm pitches) and height of 85 mm.

What compliance documentation does Schneider provide for A9F45402?

Standard documentation includes RoHS, REACH, CE, and UL declarations. The part is dual-rated to EN/IEC 60898-1 and EN/IEC 60947-2. Documentation is available on request with the order.

MPN
A9F45402