Specification summary for panel integration
The Schneider Electric A9F57232 is a 2-pole miniature circuit breaker from the Acti9 IKQ series, rated 32 A with a C curve (magnetic trip 5–10 × In). Breaking capacity is 10 kA Icn at 415 V AC, 50/60 Hz, per EN 60898-1 — sufficient for most commercial and light industrial distribution boards where the prospective fault current stays under that threshold. Thermal-magnetic trip unit covers overload and short-circuit protection. The 2-pole version protects both phase conductors in a single-phase or split-phase circuit; no earth-leakage function is integrated. Depth is 78.5 mm, height 85 mm — fits standard distribution enclosures with typical wiring space.
Limitation class 3 per that standard means the breaker limits let-through energy effectively for downstream equipment protection. IP20 finger protection on the front face; suitable for installation in enclosed distribution boards where the front is the only accessible surface.