Schneider Electric A9F68102 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F68102 Acti9 iT60 MCB, 2 A, C-curve, 1P

MPNA9F68102
Active

Schneider Electric Acti9 iT60 miniature circuit breaker, A9F68102, 2 A rated current, C-curve, 1 pole, 50 kA breaking capacity at 240 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F68102 — Identification
ParameterValue
Product nameActi9 iT60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiT60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F68102 — Electrical & Protection
ParameterValue
Rated current (In)2 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)50 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
A9F68102 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Width18 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F68102 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
A9F68102 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F68102 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

What this MCB does on the rail

The Schneider Electric A9F68102 is a 2 A, 1-pole miniature circuit breaker from the Acti9 iT60 series, built to protect final subcircuits in distribution boards. Rated breaking capacity hits 50 kA Icu at 240 V AC per EN/IEC 60947-2, and 6 kA Icn at 230 V AC per EN/IEC 60898-1. That dual rating means it covers both industrial panel duty (60947-2) and residential/commercial branch circuits (60898-1) — one part for the BOM, two standards ticked.

Terminals accept 1–25 mm² rigid or 1–16 mm² flexible — enough for the 2 A feed. Removable comb busbar compatible for multi-pole ganging.

Thermal-magnetic trip unit: the thermal bimetal handles sustained overloads; the magnetic coil clears short-circuits. Rated insulation voltage (Ui) is 500 V AC — fine for 230/400 V networks. Overvoltage category IV means it's rated for the main distribution point, not just sub-panels. Suitability for isolation is confirmed per both standards, so you can use it as a local disconnect.