Skip to main content
Schneider Electric A9F68120

Schneider Electric A9F68120 Acti9 iT60 MCB, 20 A, 1P, C-Curv

MPN A9F68120
Obsolete

Schneider Electric Acti9 iT60, A9F68120, miniature circuit breaker, 1P, 20 A, C-curve, 10 kA Icu at 230 V AC, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F68120 specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Width18 mm
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The A9F68120 is a 20 A, 1-pole miniature circuit breaker from the Schneider Acti9 iT60 series, built for distribution panels where the C-curve handles moderate inrush — motor starters, small transformers, capacitor banks — without nuisance tripping on start-up. The magnetic trip threshold is fixed at 8 x In ±20 %, so it clears a short-circuit at roughly 160 A or above, while the thermal-magnetic element protects the cable against sustained overload. Breaking capacity is the headline selector: 10 kA Icu at 220…240 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1). That dual rating means the part qualifies for industrial panel coordination (60947-2) and residential/commercial final-circuit duty (60898-1). At 12…60 V DC it holds 15 kA Icu, so it also works in DC sub-distribution for control power supplies or battery-backed loads.

It carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1, plus tropicalisation per EN/IEC 60068-2-78 (95 % RH, 55 °C). That means it is accepted in both industrial control panels and final-distribution boards across most jurisdictions. The isolation marking (suitability for isolation: yes per both standards) confirms it can be used as a disconnecting means where local code requires it.

The toggle actuator and trip-indicator window give local status without opening the panel door. Overvoltage category IV suits it for the main distribution board, not just sub-circuits.

MPN
A9F68120