Schneider Electric A9F68125 — 1-Pole MCB (DIN Rail)

A9F68125 Acti9 iT60 MCB, 25 A, C-curve, 1P, 10 kA

MPNA9F68125
Obsolete

Schneider Electric Acti9 iT60 miniature circuit breaker, A9F68125, 25 A rated current, C-curve, 1-pole, 10 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F68125 — Identification
ParameterValue
Product nameActi9 iT60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiT60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F68125 — Electrical & Protection
ParameterValue
Rated current (In)25 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
A9F68125 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Width18 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F68125 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
A9F68125 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F68125 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F68125 is a 1-pole miniature circuit breaker from the Acti9 iT60 series, rated 25 A with a C-curve trip characteristic. It protects branch circuits against overloads and short circuits in distribution panels. Breaking capacity is 10 kA Icu at 220…240 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1), enough for most commercial and light industrial distribution boards.

The removable comb busbar simplifies daisy-chaining in multi-pole groups. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire; strip length 14 mm, tightening torque 2 N·m. IP20 finger-safe protection on the front face.

Dual-certified to EN/IEC 60898-1 (MCB standard for household and similar installations) and EN/IEC 60947-2 (low-voltage switchgear for industrial applications). Suitability for isolation is confirmed under both standards. Pollution degree 3 (industrial environment), overvoltage category IV (main incoming supply), tropicalisation level 2 per EN/IEC 60068-2-78 (damp heat, 95 % RH).

Frequently asked questions

What is A9F68125's breaking capacity at 230 V AC?

At 230 V AC 50/60 Hz, the A9F68125 has a breaking capacity of 10 kA Icu per EN/IEC 60947-2 and 6 kA Icn per EN/IEC 60898-1.

What is the closest alternative to A9F68125 in the Acti9 family?

Within the Acti9 iT60 range, the closest alternative would be a different rated current (e.g., 20 A or 32 A) or a different curve (B or D) — the physical footprint and breaking capacity are shared across the series.

Where can I buy A9F68125 and how is it quoted?

The A9F68125 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN