Schneider Electric A9F68132 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F68132 Acti9 iT60 MCB, C-Curve 32 A 1P

MPNA9F68132
Obsolete

Schneider Electric Acti9 iT60N, A9F68132, miniature circuit breaker, 1P, 32 A, C-curve, 18 mm, DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68132 — Identification
ParameterValue
Product nameActi9 iT60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiT60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F68132 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
A9F68132 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Width18 mm
Tightening torque (by circuit)3.5 N.m top or bottom
A9F68132 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
A9F68132 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F68132 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F68132 is an Acti9 iT60N miniature circuit breaker (MCB) — a 1-pole, 32 A, C-curve unit built for distribution boards. It carries dual certification to EN/IEC 60898-1 and EN/IEC 60947-2, which means it qualifies for both residential/commercial branch circuits (60898-1) and industrial feeder duty (60947-2).

Breaking capacity — the number that decides fit

This breaker's interrupting capacity changes with voltage, and the right rating for your system is the one that matches your fault current. At 220…240 V AC it's rated 10 kA Icu per IEC 60947-2, and 6 kA Icn per IEC 60898-1 at 230 V AC. At 12…60 V DC it handles 15 kA Icu.

Snaps onto a DIN rail (EN/IEC 60715) and occupies two 9 mm pitches — 18 mm total width. The removable comb busbar installs on top or bottom. Terminals accept 1…35 mm² rigid or 1…25 mm² flexible, with a 3.5 N·m tightening torque. IP20 B finger protection on the front; the back is open to the enclosure. Stripping length is 14 mm.

Frequently asked questions

Where can I buy the A9F68132 and get a price?

The A9F68132 is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is the breaking capacity of the A9F68132 at 240 V AC?

10 kA Icu at 220…240 V AC per EN/IEC 60947-2, and 6 kA Icn at 230 V AC per EN/IEC 60898-1.

What compliance documentation does Schneider provide for the A9F68132?

The breaker is certified to EN/IEC 60898-1 and EN/IEC 60947-2, with tropicalisation per EN/IEC 60068-2-78. Standard Schneider declarations (CE, UKCA, RoHS) apply to the Acti9 range.

MPN