Skip to main content
Schneider Electric A9F68163 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F68163 Acti9 iT60 MCB, 63 A, 1P, C-Curv

MPNA9F68163
Obsolete

Schneider Electric Acti9 iT60, A9F68163, miniature circuit breaker, 1P, 63 A, C-curve, 36 kA Icu at 12-60 VAC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68163 — Identification
ParameterValue
Product nameActi9 iT60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiT60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F68163 — Electrical & Protection
ParameterValue
Rated current (In)63 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
A9F68163 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Width18 mm
Tightening torque (by circuit)3.5 N.m top or bottom
A9F68163 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
A9F68163 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F68163 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

What this 63 A C-curve MCB is for

The Schneider Electric A9F68163 is a 1-pole Acti9 iT60 miniature circuit breaker rated 63 A with a C-curve trip characteristic.

This breaker carries a 36 kA Icu at 12-60 VAC (EN/IEC 60947-2) and 20 kA Icu at 100-133 VAC, dropping to 10 kA Icu at 220-240 VAC. Under EN/IEC 60898-1 it is rated 6 kA Icn at 230 VAC.

Snaps onto a DIN rail (EN/IEC 60715). Terminals accept 1-35 mm² rigid or 1-25 mm² flexible copper; torque to 3.5 N·m. The removable comb busbar (installed) lets you daisy-chain phases across adjacent breakers without extra wiring. IP20B finger-safe terminals — suitable for enclosed panels only, not outdoor exposed mounting.

Suitability for isolation is confirmed under both standards. Pollution degree 3 (industrial environment). Overvoltage category IV. Tropicalisation class 2 per EN/IEC 60068-2-78 (95 % RH).

Frequently asked questions

Where can I buy A9F68163 and how do I get a price?

The A9F68163 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for a firm quote.

What is A9F68163's breaking capacity at 240 VAC?

At 220-240 VAC the A9F68163 is rated 10 kA Icu per EN/IEC 60947-2 and 6 kA Icn per EN/IEC 60898-1.

What wire sizes does the A9F68163 accept?

Terminals accept 1-35 mm² rigid or 1-25 mm² flexible copper, with a stripping length of 14 mm and torque to 3.5 N·m.

MPN