Schneider Electric A9F68210 — 2-Pole MCB (DIN Rail)

Schneider A9F68210 Acti9 iT60 MCB, 10 A C Curve 2P, 36 mm

MPNA9F68210
Active

Schneider Electric Acti9 iT60 miniature circuit breaker, A9F68210, 10 A rated current, C curve, 2 poles, 36 mm width, dual-rated EN/IEC 60898-1 and 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F68210 — Identification
ParameterValue
Product nameActi9 iT60
Series / familyActi9
Device short nameiT60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F68210 — Electrical
ParameterValue
Rated current [In]10 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
A9F68210 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
A9F68210 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Terminal connectionsSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F68210 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 %
A9F68210 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68210 is a 10 A, C-curve, 2-pole miniature circuit breaker from the Acti9 iT60 series. Breaking capacity is the key selection parameter here. The A9F68210 carries 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V per EN/IEC 60947-2. That 10 kA at 400 V covers most panelboard applications; the 20 kA at 240 V gives headroom for high-fault service entrances.

Panel integration

Mounts on DIN rail with a removable comb busbar installed. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; tightening torque is 2 N·m. The IP20 B finger-safe terminals meet IEC 60529 for panel interior use. The toggle actuator and trip indicator give local visual status.

Frequently asked questions

What is the breaking capacity of A9F68210 at 400 V?

Under EN/IEC 60898-1 the Icn is 10 kA at 400 V AC. Under EN/IEC 60947-2 the Icu is 10 kA at 380–415 V AC and 6 kA at 440 V AC.

What standards does the A9F68210 comply with?

It is dual-rated to EN/IEC 60898-1 and EN/IEC 60947-2, with pollution degree 3 and overvoltage category IV.

What is the width of the A9F68210?

The A9F68210 is 36 mm wide, occupying 4 x 9 mm pitches on a DIN rail.

Where can I buy the A9F68210?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.