Skip to main content
Schneider Electric A9F68232 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F68232 Acti9 iT60 MCB, 32 A, C Curve, 2

MPNA9F68232
Active

Schneider Electric Acti9 iT60 miniature circuit-breaker, A9F68232, 32 A, C curve, 2-pole, 36 mm wide, DIN rail mount, dual certified EN/IEC 60947-2 and EN/IEC 60898-1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68232 — Identification
ParameterValue
Product nameActi9 iT60
Series / familyActi9
Device short nameiT60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F68232 — Electrical
ParameterValue
Rated current [In]32 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
A9F68232 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
A9F68232 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Terminal connectionsSingle terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F68232 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 %
A9F68232 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68232 is an Acti9 iT60 miniature circuit-breaker (MCB) rated 32 A with a C curve, in a 2-pole (2P) configuration. Breaking capacity is rated per both standards: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V under EN/IEC 60947-2, plus 10 kA Icn at 400 V under EN/IEC 60898-1. For a 32 A MCB on a 400 V supply, the 10 kA rating covers most secondary distribution panels with transformer-limited fault current. The dual certification means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) applications — useful when a single BOM must satisfy both IEC worlds. Thermal-magnetic trip technology with Category A utilization (no intentional short-time delay) makes this a straightforward branch-circuit protector. The IP20 B finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible wire; tightening torque is 3.5 N.m.

Deployment context

The removable comb busbar allows daisy-chaining multiple MCBs in a row — typical for lighting, socket-outlet, or small-power circuits in commercial buildings and light industrial switchboards.

Frequently asked questions

Where can I buy A9F68232?

The A9F68232 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does A9F68232 comply with?

The A9F68232 is dual certified to EN/IEC 60947-2 and EN/IEC 60898-1, covering both industrial and residential/commercial applications.

What is the breaking capacity of A9F68232 at 400 V?

At 400 V AC, the A9F68232 has a breaking capacity of 10 kA Icn per EN/IEC 60898-1 and 10 kA Icu per EN/IEC 60947-2.

MPN