Skip to main content
Schneider Electric A9F68240

Schneider Electric A9F68240 Acti9 iT60 MCB, 40 A, C Curve, 2

MPN A9F68240
Obsolete

Schneider Electric Acti9 iT60, miniature circuit breaker, 40 A, C curve, 2P, 36 kA breaking capacity, DIN rail mount, thermal-magnetic trip.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F68240 specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Width36 mm
ApplicationDistribution
Operating temperature-35...70 °C

Product details

What the 36 kA breaking capacity means for your panel

The A9F68240 is a 40 A, 2-pole miniature circuit breaker from the Schneider Acti9 iT60 range, with a C curve and thermal-magnetic trip unit. Its headline rating is a 36 kA breaking capacity (Icu) at 12–133 V AC, which drops to 20 kA at 220–240 V and 10 kA at 380–415 V — the figure that governs your SCCR coordination downstream.

DIN-rail integration and terminal work

Terminals accept 1–35 mm² rigid or 1–25 mm² flexible copper; strip 14 mm and torque to 3.5 N.m. The removable comb busbar is installed from the factory, so you can daisy-chain phases across adjacent breakers without extra wiring. IP20 B finger-safe protection on the front face; the back and terminals are live when busbar is energized — standard for this class.

Standards compliance and approvals

Dual-rated to EN/IEC 60898-1 (for household and similar installations) and EN/IEC 60947-2 (for industrial applications). Suitability for isolation is confirmed under both standards. Tropicalisation class 2 per EN/IEC 60068-2-78 (95% RH at 55 °C) covers humid environments without derating.

MPN
A9F68240