Schneider Electric A9F68240 Acti9 iT60 MCB, 40 A, C Curve, 2

MPNA9F68240
Obsolete

Schneider Electric Acti9 iT60, miniature circuit breaker, 40 A, C curve, 2P, 36 kA breaking capacity, DIN rail mount, thermal-magnetic trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68240 — Identification
ParameterValue
Product nameActi9 iT60
Series / familyActi9
Device short nameiT60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F68240 — Electrical
ParameterValue
Rated current [In]40 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9F68240 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
A9F68240 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Terminal connectionsSingle terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F68240 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 %
A9F68240 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

What the 36 kA breaking capacity means for your panel

The A9F68240 is a 40 A, 2-pole miniature circuit breaker from the Schneider Acti9 iT60 range, with a C curve and thermal-magnetic trip unit. Its headline rating is a 36 kA breaking capacity (Icu) at 12–133 V AC, which drops to 20 kA at 220–240 V and 10 kA at 380–415 V — the figure that governs your SCCR coordination downstream.

DIN-rail integration and terminal work

Terminals accept 1–35 mm² rigid or 1–25 mm² flexible copper; strip 14 mm and torque to 3.5 N.m. The removable comb busbar is installed from the factory, so you can daisy-chain phases across adjacent breakers without extra wiring. IP20 B finger-safe protection on the front face; the back and terminals are live when busbar is energized — standard for this class.

Standards compliance and approvals

Dual-rated to EN/IEC 60898-1 (for household and similar installations) and EN/IEC 60947-2 (for industrial applications). Suitability for isolation is confirmed under both standards. Tropicalisation class 2 per EN/IEC 60068-2-78 (95% RH at 55 °C) covers humid environments without derating.

Frequently asked questions

Where can I buy A9F68240 and how do I get a price?

The A9F68240 is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is A9F68240's breaking capacity at 400 V?

At 400 V AC 50/60 Hz, the A9F68240 has a 10 kA Icn per EN/IEC 60898-1 and a 10 kA Icu at 380–415 V per EN/IEC 60947-2.

What does the C curve mean on this breaker?

The C curve means the magnetic trip threshold is 5 to 10 times the rated current (In). For the 40 A A9F68240, the magnetic tripping limit is 8 x In ±20%, so it trips magnetically between roughly 256 A and 384 A — suited for general-purpose loads like lighting, socket circuits, and small motors with moderate inrush.

MPN