It breaks up to 50 kA Icu at 415 V AC (EN/IEC 60947-2) and carries a 10 kA Icn at 400 V (EN/IEC 60898-1), so it handles high fault currents typical in distribution panels while still meeting residential-standard coordination.
Rated Icu of 50 kA at 220–240 V and 380–415 V AC per EN/IEC 60947-2. C curve trips magnetically at 8 x In ±20 %. Suitability for isolation per both standards.
Snaps onto DIN rail, occupies 54 mm (6 x 9 mm pitches). Terminals accept 1–25 mm² rigid or 1–16 mm² flexible; tightening torque 2 N·m. Removable comb busbar. IP20 finger-safe terminals, pollution degree 3, overvoltage category IV — rated for the main distribution board, not just sub-panels. Ambient operation from -35 to 70 °C covers most indoor enclosures even near hot busbars.
Lifecycle status is current. Standard catalogue item in the Acti9 range.