Skip to main content
Schneider Electric A9F68306 — Miniature Circuit Breakers (MCB)

A9F68306 Acti9 iT60 MCB, 6 A, C Curve, 3P, 36 kA

MPNA9F68306
Active

Schneider Electric Acti9 iT60, A9F68306, miniature circuit-breaker, 6 A, C curve, 3 poles, 36 kA Icu at 133 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68306 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68306 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68306 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68306 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Number of 9 mm pitches6
A9F68306 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68306 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68306 is a 6 A, 3-pole miniature circuit-breaker from the Acti9 iT60 range, carrying a C curve for moderate inrush loads like small motors or lighting circuits. Rated insulation voltage is 500 V AC, and the breaking capacity reaches 36 kA Icu at 133 V AC, stepping down to 10 kA at 400 V AC under the 60947-2 standard. The thermal-magnetic trip unit has a magnetic threshold of 8 x In ±20%.

At 220–240 V AC the rating drops to 20 kA, and at 380–415 V AC it holds at 10 kA — sufficient for most European low-voltage distribution panels. The limitation class is 3, meaning it limits let-through energy effectively for downstream equipment protection.

Snap-on DIN rail mounting per EN/IEC 60715. The 54 mm width (6 x 9 mm pitches) occupies three modular spaces in the panel. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; tightening torque is 2 N·m. The removable comb busbar is pre-installed for daisy-chaining phases.

Frequently asked questions

How do I get current pricing and availability for A9F68306?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9F68306's breaking capacity at 400 V?

Under EN/IEC 60947-2 the Icu is 10 kA at 380–415 V AC; under EN/IEC 60898-1 the Icn is 10 kA at 400 V AC.

What wire sizes does the A9F68306 terminal accept?

Single terminal accepts 1–25 mm² rigid or 1–16 mm² flexible wire, top or bottom. Strip length is 14 mm, tightening torque 2 N·m.

MPN
A9F68306