Skip to main content
Schneider Electric A9F68325 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F68325 Acti9 iT60 MCB, 25 A, C Curve, 3

MPNA9F68325
Active

Schneider Electric Acti9 iT60, A9F68325, miniature circuit breaker, 25 A, C curve, 3 poles, 54 mm width, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68325 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68325 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68325 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68325 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Number of 9 mm pitches6
A9F68325 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68325 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68325 is a 3-pole Acti9 iT60 miniature circuit breaker rated at 25 A with a C curve, built for distribution boards on DIN rail.

The A9F68325 delivers 36 kA Icu at 12–133 V AC, 20 kA Icu at 220–240 V AC, and 10 kA Icu at 380–415 V AC per IEC 60947-2. That 20 kA at 240 V is the number most panel builders care about for a 25 A C-curve MCB in a North American or European distribution board — it means this breaker can safely interrupt a 20,000 A fault without welding its contacts or bursting the case. At 400 V, the Icn per IEC 60898-1 is 10 kA, which covers the standard domestic/commercial fault level. The utilisation category is A, so it's not intended for motor switching under load — use a contactor for that.

What the C curve and thermal-magnetic trip mean on the route

The thermal-magnetic trip unit handles overloads (thermal bimetal) and short-circuits (solenoid) in one package. Magnetic tripping limit is 8 x In, so at 25 A that's 200 A instantaneous trip — fast enough to protect wiring but tolerant of the inrush from a small motor or a bank of contactor coils. The thermal element is tropicalised to class 2 per EN/IEC 60068-2-78, meaning it holds up in high-humidity environments without nuisance tripping from corrosion on the bimetal.

Snaps onto DIN rail, 54 mm wide (6 x 9 mm pitches). Terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper, with a tightening torque of 2 N·m. The removable comb busbar is installed from the factory — you can daisy-chain the line side across multiple breakers without extra wiring. Pollution degree 3 per IEC 60947-2, meaning it's rated for conductive dust and condensation typical in industrial enclosures.

Frequently asked questions

Where can I buy A9F68325 and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What standards does the A9F68325 comply with?

It is dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial), with suitability for isolation per both standards. Pollution degree 3, overvoltage category IV, and tropicalisation class 2 per EN/IEC 60068-2-78.

What is the breaking capacity of A9F68325 at 240 V?

The breaking capacity is 20 kA Icu at 220–240 V AC per IEC 60947-2, and 10 kA Icn at 400 V per IEC 60898-1.

MPN
A9F68325