Skip to main content
Schneider Electric A9F68402 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F68402 Acti9 iT60 MCB, 2A C-Curve 4P 50

MPNA9F68402
Active

Schneider Electric Acti9 iT60N, A9F68402, miniature circuit breaker, 4P, 2 A, C-curve, 50 kA Icu at 415 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68402 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68402 — Ratings
ParameterValue
Rated current (In)2 A
Poles configuration4P
Number of protected poles4
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68402 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68402 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Number of 9 mm pitches8
A9F68402 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68402 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68402 is an Acti9 iT60N miniature circuit breaker — 4 poles, 2 A rated current, C-curve. That dual rating means it fits a distribution board or an industrial sub-panel without re-certifying the assembly.

This breaker delivers 50 kA Icu at 415 V AC (50/60 Hz) under EN/IEC 60947-2, and 10 kA Icn at 400 V under EN/IEC 60898-1. For most industrial panels fed by a transformer of 1 MVA or less, 50 kA gives you solid headroom for selectivity coordination downstream. At 440 V it still holds 25 kA, so you're covered on 480 V-class systems.

C-curve trip and 2 A rating — what it protects

For a 2 A breaker, that's 10 to 20 A instantaneous — ideal for general-purpose distribution loads like lighting, small transformers, or control circuits that don't have a high inrush. The 2 A rating is on the low side; you'd use it to protect a 0.5 kVA control transformer or a string of PLC power supplies, not a motor branch.

Width is 72 mm — that's 8 modules of 9 mm pitch, so it takes up 8 TE (terminal unit) spaces in an enclosure.

Frequently asked questions

Where can I buy A9F68402 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is A9F68402's breaking capacity at 415 V?

50 kA Icu at 380…415 V AC 50/60 Hz per EN/IEC 60947-2. At 440 V it's 25 kA Icu.

What compliance documentation does this brand provide for A9F68402?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It also carries tropicalisation compliance per EN/IEC 60068-2-78 (95 % RH).

MPN
A9F68402