Skip to main content
Schneider Electric A9F68406 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F68406 Acti9 iT60 MCB, 6A C-Curve 4P 36

MPNA9F68406
Active

Schneider Electric Acti9 iT60, A9F68406, miniature circuit breaker, 6 A, C-curve, 4P, 36 kA breaking capacity at 133 V AC, thermal-magnetic trip, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68406 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68406 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68406 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68406 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Number of 9 mm pitches8
A9F68406 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68406 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68406 is a 6 A, 4-pole miniature circuit breaker from the Acti9 iT60 series, with a C-curve trip characteristic.

Breaking capacity varies by voltage: 36 kA Icu at 12…133 V AC, 20 kA at 220…240 V, 10 kA at 380…415 V, and 6 kA at 440 V, all per EN/IEC 60947-2. Under EN/IEC 60898-1 it is rated 10 kA Icn at 400 V. The 36 kA figure at low voltage is useful for high-fault panels where the upstream transformer is close; at 400 V the 10 kA Icu still covers most European commercial installations.

Snaps onto DIN rail, 72 mm wide (8 x 9 mm pitches). Terminals accept 1…25 mm² rigid or 1…16 mm² flexible, with a tightening torque of 2 N·m. The removable comb busbar is pre-installed, so daisy-chaining phases across a row of MCBs is straightforward — no extra busbar to order for the common feed. IP20 finger-safe terminals, pollution degree 3, overvoltage category IV.

Frequently asked questions

Where can I buy A9F68406 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for your quantity; availability and current pricing are confirmed at quote time.

What is the breaking capacity of A9F68406 at 400 V?

10 kA Icu at 380…415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1.

What is the rated current and pole configuration?

6 A rated current, 4 poles (4P), C-curve trip characteristic.

MPN
A9F68406