Overview
The A9F86116 is a 1-pole Acti 9 iC60 miniature circuit breaker rated 16 A with a B-curve magnetic trip at 4 x In ±20 %, delivering a 42 kA ICu breaking capacity at 60 V AC/DC.
Compared to the A9F83104 (4 A, 70 kA ICu), the A9F86116 offers a higher 16 A rating but a lower 42 kA ICu — pick the A9F86116 when the load requires 16 A and the available fault current stays under 42 kA; choose the A9F83104 when the panel SCCR demands 70 kA at a lower 4 A load.