Schneider Electric A9FDB616 — 1-Pole MCB (DIN Rail)

Schneider Electric A9FDB616 Acti9 iDPN N Arc, 16 A C-Curve A

MPNA9FDB616
Obsolete

Schneider Electric Acti9 iDPN N Arc, arc fault detection circuit breaker, 1P+N, 16 A, C-curve, 6 kA Icn at 230 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9FDB616 — Identification
ParameterValue
Product nameActi9 iDPN N Arc
Product / component typeArc fault detection circuit breaker
Product rangeActi9
Device short nameiDPN N Arc
Poles description1P + N
Number of protected poles1
A9FDB616 — Electrical & Protection
ParameterValue
Rated current (In)16 A at 30 °C
Rated operational voltage (Ue)230 V AC 50 Hz conforming to IEC 62606 230 V AC 50 Hz conforming to EN/IEC 60898-1
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9FDB616 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal for 1 cable(s) 10 mm² flexible Tunnel type terminal for 2 cable(s) 2.5 mm² flexible Tunnel type terminal for 1 cable(s) 16 mm² rigid Tunnel type terminal for 2 cable(s) 2.5 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height81 mm
Depth72 mm
Tightening torque (by circuit)2 N.m
A9FDB616 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9FDB616 — Approvals
ParameterValue
Conformity standardsEN/IEC 62606 IEC 60898-1
A9FDB616 — Electrical
ParameterValue
[Ui] rated insulation voltage400 V AC
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

Arc fault detection circuit breaker, 1P+N, 16 A C-curve

The Schneider Electric A9FDB616 is an Acti9 iDPN N Arc arc fault detection circuit breaker (AFDD) — a single-module (36 mm wide) 1P+N device that combines a 16 A thermal-magnetic MCB with series arc fault detection per EN/IEC 62606. Breaking capacity is 6000 A Icn at 230 V AC 50 Hz, conforming to IEC 60898-1 — sufficient for residential and light commercial final circuits where the prospective short-circuit current stays under 6 kA. The limitation class 3 (per IEC 60898-1) means it limits let-through energy well enough to protect downstream wiring in most final subcircuits. Rated current of 16 A is specified at 30 °C; standard thermal derating applies for higher ambient temperatures inside a panel.

DIN rail integration and wiring

Neutral is on the left, phase on the right, with a 9 mm pitch between phase and neutral terminals. The toggle actuator provides ON/OFF and fault-trip indication via the local signalling window.

Frequently asked questions

How do I get current pricing and availability for A9FDB616?

Submit an RFQ through the storefront; pricing and stock are confirmed at quote time through independent distribution.

What is A9FDB616's listed depth?

The A9FDB616 has a depth of 72 mm, width 36 mm, height 81 mm — a single-module 1P+N footprint.

What standards does the A9FDB616 comply with?

It complies with EN/IEC 62606 (arc fault detection device standard) and IEC 60898-1 (MCB standard).

MPN