Schneider Electric A9FDB7613 — 2-Pole MCB (DIN Rail)

A9FDB7613 Fire Protection Switch, 2-Pole, 13 A, B-Curve, 6 k

MPNA9FDB7613

Schneider Electric iDPN N Arc fire protection switch + LS, 2-pole, 13 A, B-curve, 6 kA breaking capacity, DIN rail mount.

$74.86 – $83.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9FDB7613 — Protection
ParameterValue
Overvoltage categoryIII
A9FDB7613 — Mechanical
ParameterValue
Width36 mm
Height81 mm
Depth72 mm
A9FDB7613 — Other specifications
ParameterValue
Poles2
Frequency50 Hz
IP ratingIP20
MountingDIN Rail Mount
Current13 A
Tripping mechanismThermal Magnetic
Terminal contact typeTunnel Terminals
Voltage400 V
Tripping characteristicsB
Tightening torque - Screw-Type max.2 Nm
Rated Short-Circuit breaking capacity icn6 kA

Product details

The A9FDB7613 is a 2-pole combination fire protection switch and miniature circuit breaker from the iDPN N Arc family. The thermal-magnetic trip mechanism handles both overloads (slow thermal) and faults (fast magnetic). Rated insulation voltage is 400 V, and the short-circuit breaking capacity (Icn) is 6 kA — enough for most final subcircuits in a 400/230 V distribution board. The overvoltage category III rating means it's designed for fixed installations inside the building's main panel, not for outlet-level use. It's 50 Hz only, so don't spec it for 60 Hz systems without checking the manufacturer's derating.

DIN rail mount, 36 mm wide (2 modules), 81 mm tall, 72 mm deep. The tunnel terminals accept screw-clamp wiring up to 2 Nm torque. IP20 means it's for dry indoor panels only — no washdown, no dust. This is a panel-board part, not a field device.

Frequently asked questions

What is the breaking capacity of the A9FDB7613?

The rated short-circuit breaking capacity Icn is 6 kA at 400 V, 50 Hz.

What is the tripping characteristic of this breaker?

B-curve — trips magnetically between 3 and 5 times rated current (39 A to 65 A for this 13 A unit).

Can I use this on a 60 Hz system?

The listed frequency is 50 Hz. Using it on 60 Hz without manufacturer confirmation is not recommended.