Schneider Electric A9K23110 — 1-Pole MCB (DIN Rail)

Schneider Electric A9K23110 Acti9 iK60 MCB, B Curve, 10 A, 1

MPNA9K23110
Active

Schneider Electric Acti9 iK60N, miniature circuit breaker, 1P, 10 A, B curve, 6 kA Icn at 230 V AC, clip-on DIN rail, white.

$6.23Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9K23110 — Identification
ParameterValue
Product nameActi9 iK60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiK60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9K23110 — Electrical & Protection
ParameterValue
Rated current (In)10 A at 30 °C
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9K23110 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9K23110 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9K23110 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9K23110 — Electrical
ParameterValue
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60898-1

Product details

The Schneider Electric A9K23110 is an Acti9 iK60N miniature circuit breaker (MCB), single-pole, rated 10 A at 30 °C with a B tripping curve. That B curve means magnetic trip occurs between 3 and 5 times the rated current — so for a 10 A breaker, instantaneous trip starts at 30 A and is guaranteed by 50 A. This makes it the go-to for resistive or general-purpose loads where you want short-circuit protection without nuisance tripping from modest inrush.

Breaking capacity and standard compliance

Rated breaking capacity is 6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That 6 kA figure is the standard domestic and light-commercial fault level — sufficient for most distribution boards fed from a typical transformer. The breaker also carries a limitation class 3 rating under the same standard, meaning it lets through very little fault energy, so downstream wiring and devices see less stress during a short circuit. Insulation voltage rated 440 V AC, overvoltage category III — fits standard panel environments.

Clip-on mounting to DIN rail (EN rail). Occupies 2 x 9 mm pitches — that's 18 mm width, so a single-pole breaker takes one standard modular slot. Depth 78.5 mm, height 85 mm. Tightening torque 2 N·m.

Frequently asked questions

Where can I buy the A9K23110 and get a price?

The A9K23110 is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9K23110?

6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1.

What standards does the A9K23110 comply with?

EN/IEC 60898-1. The breaker also carries limitation class 3 and pollution degree 2 ratings under that standard.

MPN