Skip to main content
Schneider Electric A9K23203 — 2-Pole MCB (DIN Rail)

Schneider Electric A9K23203 Acti9 iK60N MCB, 3 A, B Curve, 2

MPNA9K23203
Obsolete

Schneider Electric Acti9 iK60N miniature circuit-breaker, A9K23203, 2P, 3 A, B curve, 6 kA Icn at 400 V AC, thermal-magnetic, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K23203 — Identification
ParameterValue
Product nameActi9 iK60
Series / familyActi9
Device short nameiK60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9K23203 — Electrical
ParameterValue
Rated current [In]3 A at 30 °C
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC
Network frequency50/60 Hz
A9K23203 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9K23203 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth78.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorNo
A9K23203 — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...85 °C
A9K23203 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1

Product details

The Schneider Electric A9K23203 is a 2-pole Acti9 iK60N miniature circuit-breaker rated 3 A at 30 °C with a B tripping curve (3...5 x In magnetic limit). It delivers 6 kA breaking capacity (Icn) at 400 V AC 50/60 Hz per EN/IEC 60898-1 — enough for most final-distribution branch circuits in residential or light commercial panels where the prospective fault current stays under that threshold. The thermal-magnetic trip unit covers overload and short-circuit protection for two protected poles.

Depth is 78.5 mm, height 85 mm, so it clears most shallow consumer units and distribution boards. Tunnel-type terminals accept 1...25 mm² rigid or 1...16 mm² flexible on top or bottom; wire strip length 14 mm, tightening torque 2 N·m. IP20 finger-safe protection for the front face once installed.

Frequently asked questions

What is the breaking capacity of A9K23203?

6 kA Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 — sufficient for most final sub-distribution boards where the prospective short-circuit current stays under that level.

What does the B curve mean on this MCB?

The magnetic trip operates at 3 to 5 times the rated current (3...5 x In), so a 3 A breaker trips instantaneously between 9 A and 15 A. B curve is standard for resistive or general-purpose loads where inrush is low — lighting, socket outlets, control transformers.

Where can I buy the A9K23203?

This part is sourced and quoted to order against an RFQ through independent distribution. Contact us for current pricing and availability — confirmed at quote time.

MPN
A9K23203