Skip to main content
Schneider Electric A9K23232 — 2-Pole MCB (DIN Rail)

Schneider Electric A9K23232 Acti9 iK60N MCB, 32 A B-Curve 2P

MPNA9K23232
Obsolete

Schneider Electric Acti9 iK60N, A9K23232, miniature circuit breaker, 32 A, B-curve, 2P, 6000 A Icn at 400 V AC, thermal-magnetic, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K23232 — Identification
ParameterValue
Product nameActi9 iK60
Series / familyActi9
Device short nameiK60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9K23232 — Electrical
ParameterValue
Rated current [In]32 A at 30 °C
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC
Network frequency50/60 Hz
A9K23232 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9K23232 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth78.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorNo
A9K23232 — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...85 °C
A9K23232 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1

Product details

The Schneider Electric A9K23232 is an Acti9 iK60N miniature circuit breaker rated 32 A at 30 °C, B-curve, 2-pole, with a 6000 A Icn breaking capacity at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1.

Clip-on mounting on a 36 mm wide DIN rail, occupying 4 x 9 mm pitches. The 2-pole body is 36 mm wide, 85 mm tall, 78.5 mm deep — fits standard distribution boards and sub-panels. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; tighten to 3.5 N.m. Strip 14 mm of insulation. Padlocking provision for lockout/tagout.

Frequently asked questions

Where can I buy A9K23232?

The A9K23232 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9K23232's breaking capacity?

The A9K23232 has a 6000 A Icn breaking capacity at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1. This means it safely interrupts fault currents up to 6 kA in a 400 V distribution circuit.

What is the B-curve on this MCB?

The B-curve means the magnetic trip operates at 3 to 5 times the rated current (In). For the 32 A A9K23232, that's 96 to 160 A instantaneous trip — suited for resistive loads and general-purpose circuits with low inrush.

What compliance documentation does Schneider provide for A9K23232?

The A9K23232 is designed and tested to EN/IEC 60898-1. It carries CE marking for the European market. For specific RoHS, REACH, or UL documentation, request the compliance declaration at quote time.

MPN