Skip to main content
Schneider Electric A9K23606 — 1-Pole MCB (DIN Rail)

Schneider Electric A9K23606 Acti9 iK60N MCB, 6 A, Curve B, 1

MPNA9K23606
Obsolete

Schneider Electric Acti9 iK60N miniature circuit breaker, A9K23606, 6 A rated current, curve B, 1P+N, 6 kA breaking capacity, DIN-rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K23606 — Identification
ParameterValue
Product nameActi9 iK60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiK60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9K23606 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 30 °C
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9K23606 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...25 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height85 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9K23606 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9K23606 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9K23606 — Electrical
ParameterValue
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60898-1

Product details

The Schneider Electric A9K23606 is an Acti9 iK60N miniature circuit breaker (MCB) rated 6 A at 30 °C, curve B, 1P+N, with a 6 kA breaking capacity at 230 V AC.

Curve B (magnetic trip 3...5 x In) means it trips instantaneously between 18 A and 30 A — suited for resistive or general-purpose loads with low inrush, like lighting circuits or socket outlets. The 1P+N configuration switches the phase and disconnects the neutral without protecting it — the neutral pole is a switched neutral, not a protected pole. Pollution degree 2 is the standard for normal, non-condensing indoor environments.

The toggle actuator provides local ON/OFF indication.

Frequently asked questions

What is the breaking capacity of A9K23606?

The A9K23606 has a breaking capacity of 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1.

Where can I buy A9K23606 and how is it quoted?

The A9K23606 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does A9K23606 comply with?

The A9K23606 complies with EN/IEC 60898-1, with limitation class 3 and pollution degree 2 per that standard.

MPN