The A9K23625: Clip-on mounting on standard DIN rail (EN 60715). The 36 mm width (4 x 9 mm pitches) and 85 mm height leave room for adjacent devices in a populated enclosure; depth at 78.5 mm means it clears most shallow consumer units. Neutral is on the left — verify busbar orientation if replacing an older board with reversed neutral.
Schneider Electric A9K23625 Acti9 iK60N MCB, 25 A, Curve B,
Schneider Electric Acti9 iK60N, miniature circuit breaker, A9K23625, 1P+N, 25 A, curve B, 6 kA at 230 V AC, thermal-magnetic, clip-on DIN rail.
Specifications
| Parameter | Value |
|---|---|
| Product name | Acti9 iK60 |
| Product / component type | Miniature circuit-breaker |
| Product range | Acti9 |
| Device short name | iK60N |
| Poles description | 1P + N |
| Number of protected poles | 1 |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 25 A at 30 °C |
| Tripping curve code | B |
| Magnetic tripping limit | 3...5 x In |
| Breaking capacity (Icu / AIR) | 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Overvoltage category | III |
| Trip unit technology | Thermal-magnetic |
| Control / actuation type | Toggle |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| Terminal connections / wire range | Single terminal (top or bottom) 1...25 mm² rigid |
| Mounting support | DIN rail |
| Mounting mode | Clip-on |
| Width | 36 mm |
| Height | 85 mm |
| Depth | 78.5 mm |
| Tightening torque (by circuit) | 2 N.m top or bottom |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...60 °C |
| Storage ambient temperature | -40...85 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Parameter | Value |
|---|---|
| Conformity standards | EN/IEC 60898-1 |
| Parameter | Value |
|---|---|
| [Ui] rated insulation voltage | 440 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60898-1 |
Product details
Frequently asked questions
What is the breaking capacity of A9K23625?
6 kA Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1, sufficient for most residential and light-commercial final circuits.
What does curve B mean on this MCB?
Curve B means the magnetic trip operates at 3 to 5 times the rated current (In). For the 25 A unit, that is 75 to 125 A — suited for resistive or lighting loads with low inrush, not motor starting.
Where can I buy A9K23625 and get current pricing?
The A9K23625 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.