Skip to main content
Schneider Electric A9K24113 — 1-Pole MCB (DIN Rail)

Schneider Electric A9K24113 Acti9 iK60 MCB, 13 A, 1P, C-Curv

MPNA9K24113
Active

Schneider Electric Acti9 iK60N miniature circuit-breaker, A9K24113, 1P, 13 A, C-curve, 6000 A Icn at 230 V AC, thermal-magnetic trip, clip-on DIN rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K24113 — Identification
ParameterValue
Product nameActi9 iK60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiK60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9K24113 — Electrical & Protection
ParameterValue
Rated current (In)13 A at 30 °C
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9K24113 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9K24113 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9K24113 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9K24113 — Electrical
ParameterValue
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60898-1

Product details

The Schneider Electric A9K24113 is an Acti9 iK60N miniature circuit-breaker (MCB) rated 13 A at 30 °C, single-pole, with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). It breaks 6000 A Icn at 230 V AC 50/60 Hz, conforming to EN/IEC 60898-1 — the standard for overcurrent protection in residential and commercial distribution boards.

The 440 V rated insulation voltage (Ui) confirms the MCB is rated for the voltage stress across its open contacts in a 230/400 V system.

Panel integration

The tunnel-type terminals accept 1–25 mm² rigid or 1–16 mm² flexible cable; strip 14 mm and torque to 2 N.m. The toggle actuator provides ON/OFF indication and accepts a padlocking device for lockout/tagout. IP20 finger protection is standard for enclosed panels.

Frequently asked questions

Where can I buy A9K24113 and get a price?

The A9K24113 is available to order through independent distribution channels. Submit an RFQ for current pricing and availability — both are confirmed at quote time.

What is the breaking capacity of A9K24113?

The A9K24113 has a breaking capacity of 6000 A Icn at 230 V AC 50/60 Hz, conforming to EN/IEC 60898-1.

MPN