Skip to main content
Schneider Electric A9K24202 — 2-Pole MCB (DIN Rail)

Schneider Electric A9K24202 Acti9 iK60N MCB, 2A C-Curve 2P 6

MPNA9K24202
Active

Schneider Electric Acti9 iK60N, miniature circuit breaker, 2A, C-curve, 2P, 6kA Icn at 400V AC, EN/IEC 60898-1, clip-on DIN rail, thermal-magnetic trip, IP20.

$17.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9K24202 — Identification
ParameterValue
Product nameActi9 iK60
Series / familyActi9
Device short nameiK60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9K24202 — Electrical
ParameterValue
Rated current [In]2 A at 30 °C
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC
Network frequency50/60 Hz
A9K24202 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9K24202 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth78.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorNo
A9K24202 — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...85 °C
A9K24202 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1

Product details

The A9K24202 is a 2-pole Acti9 iK60N miniature circuit breaker rated 2 A at 30 °C with a C-curve magnetic trip (5 to 10 × In). The thermal-magnetic trip unit handles both sustained overloads (bimetal strip) and short-circuit events (solenoid). Rated insulation voltage is 440 V AC, so it's fine on 230/400 V three-phase panels. The C-curve is the default for general-purpose distribution — lighting, socket outlets, small motor loads — where inrush is moderate. For a 2 A rating that means motor starting currents up to roughly 20 A peak before the magnetic trip clears it.

Clip-on mount to standard 35 mm DIN rail. Width is 36 mm (4 × 9 mm pitches), depth 78.5 mm, height 85 mm. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; tighten to 2 N·m. Strip length 14 mm. The ON/OFF toggle provides local indication; padlocking device available for lockout/tagout. Pollution degree 2 (non-conductive, occasional condensation) and overvoltage category II cover normal residential and commercial panel conditions.

Limitation class 3 per that standard — the let-through energy is low enough to protect downstream equipment in most fault scenarios. Suitability for isolation confirmed, meaning you can safely use it as a disconnection point with the toggle off.

Frequently asked questions

How do I get pricing and availability for A9K24202?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the distributor channel; the part is sourced to order and current stock levels are checked on your inquiry.

What is the breaking capacity of A9K24202?

The breaking capacity is 6000 A Icn at 400 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That is the standard domestic/commercial fault-interruption rating for this class of MCB.

What is the closest alternative to A9K24202 in the Acti9 family?

Within the Acti9 iK60 range, the closest sibling is the single-pole version (1P) at the same 2 A C-curve rating. The 2-pole A9K24202 is the one you want when you need both line and neutral protection on a single module width of 36 mm.

MPN