Skip to main content
Schneider Electric A9K24602 — 1-Pole MCB (DIN Rail)

A9K24602 Acti9 iK60 MCB, 2A 1P+N C-curve, 6kA

MPNA9K24602
Obsolete

Schneider Electric Acti9 iK60 series, miniature circuit-breaker A9K24602, 1P+N, 2 A, C-curve, 6 kA at 230 V AC, DIN-rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K24602 — Identification
ParameterValue
Product nameActi9 iK60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiK60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9K24602 — Electrical & Protection
ParameterValue
Rated current (In)2 A at 30 °C
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9K24602 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height85 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9K24602 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9K24602 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9K24602 — Electrical
ParameterValue
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60898-1

Product details

Schneider Electric A9K24602 is an Acti9 iK60N miniature circuit-breaker rated 2 A at 30 °C, 1P+N, with a C-curve trip characteristic (magnetic tripping between 5 and 10 x In). It breaks 6000 A Icn at 230 V AC, 50/60 Hz, per EN/IEC 60898-1. That 6 kA rating covers common residential and light commercial panel faults — enough for a distribution sub-board where the upstream device limits the prospective short-circuit current.

Tunnel terminals top and bottom accept 1 to 25 mm² rigid or 1 to 16 mm² flexible; strip 14 mm and torque to 2 N·m. IP20 rated, so it stays inside a closed panel or enclosure.

Frequently asked questions

How do I get current pricing and availability for A9K24602?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is A9K24602's breaking capacity?

It is rated 6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1.

What compliance standards does A9K24602 meet?

It conforms to EN/IEC 60898-1, carries pollution degree 2 and overvoltage category II, and is rated for isolation per the same standard.

MPN
A9K24602