It is a 1-pole + neutral (1P+N) unit rated at 6 A at 30 °C, with a C-curve trip characteristic (magnetic tripping between 5 and 10 times the rated current). The thermal-magnetic trip unit provides overload protection (thermal bimetal) and short-circuit protection (magnetic coil) in a single device.
Deployment context — panel integration
The A9K24606 clips onto a standard 35 mm DIN rail (EN 60715) and occupies 4 x 9 mm pitches (36 mm width), leaving room for adjacent modules in a multi-row enclosure. The tunnel-type terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; the recommended tightening torque is 2 N.m. Wire stripping length is 14 mm. The white housing carries an ON/OFF toggle indicator and a padlocking provision for lockout/tagout during maintenance.