Skip to main content
Schneider Electric A9K24716 — Circuit Breaker Accessories

Schneider Electric A9K24716 Acti9 iK60N MCB, 16 A, C-Curve,

MPNA9K24716
Active

Schneider Electric Acti9 iK60N miniature circuit-breaker, A9K24716, 3P+N, 16 A rated current, C-curve, 6 kA breaking capacity at 400 V AC, thermal-magnetic trip, clip-on DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K24716 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product nameActi9 iK60
Product rangeActi9
Device applicationDistribution
A9K24716 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]16 A at 30 °C
Rated insulation voltage [Ui]440 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated impulse withstand voltage [Uimp]4 kV conforming to EN/IEC 60898-1
Network frequency50/60 Hz
Poles description3P + N
Magnetic tripping limit5...10 x In
A9K24716 — Protection & Performance
ParameterValue
Breaking capacity6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1
Mechanical durability20000 cycles
Electrical durability10000 cycles
Local signallingON/OFF indication
A9K24716 — Mechanical
ParameterValue
Connections / terminalsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Device short nameiK60N
Control typeToggle
Mounting modeClip-on
Mounting supportDIN rail
Usable 9 mm pitches8
Width72 mm
Height85 mm
Depth78.5 mm
ColourWhite
A9K24716 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 60898-1
Operating ambient air temperature-25...60 °C
Storage ambient air temperature-40...85 °C
A9K24716 — Approvals
ParameterValue
StandardsEN/IEC 60898-1
A9K24716 — Specifications
ParameterValue
Curve codeC
Number of protected poles3

Product details

The Schneider Electric A9K24716 is an Acti9 iK60N miniature circuit-breaker (MCB) rated 16 A at 30 °C with a C-curve trip characteristic, built to EN/IEC 60898-1. The 6 kA Icn breaking capacity at 400 V AC 50/60 Hz means it can safely interrupt a fault current up to 6 000 A without welding the contacts — enough for most residential and light commercial distribution panels where the prospective short-circuit current stays under that level. The 3P+N configuration protects all three phases and switches the neutral, which is the standard arrangement for a three-phase distribution board in a TN or TT system. It clips onto a DIN rail, occupies 8 x 9 mm pitches (72 mm wide), and stands 85 mm tall with a depth of 78.5 mm, so it fits a standard modular enclosure without surprises.

Mounting is clip-on DIN rail — no screws, just snap it onto the rail and it locks. The tunnel-type terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible wire; strip 14 mm and torque to 2 N·m. The toggle gives a clear ON/OFF indication, and there is a padlocking provision for lockout/tagout.

Frequently asked questions

What is the breaking capacity of A9K24716?

The breaking capacity is 6000 A Icn at 400 V AC 50/60 Hz, conforming to EN/IEC 60898-1. This is the standard 6 kA rating for domestic and light commercial distribution boards.

Where can I buy A9K24716?

The A9K24716 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the rated current and curve of A9K24716?

The rated current is 16 A at 30 °C, with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). The C-curve is the standard choice for general-purpose loads like lighting, socket outlets, and small motor circuits.

What compliance documentation does A9K24716 have?

The A9K24716 is certified to EN/IEC 60898-1, carries an IP20 degree of protection, and is suitable for isolation per that standard. It is a Schneider Electric Acti9 product, so full CE, UKCA, and RoHS documentation is available from the manufacturer.

MPN
A9K24716