Panel integration note — A9K24763
The Schneider Electric A9K24763 is a 63 A miniature circuit-breaker from the Acti9 iK60N series, configured as 3P+N with a C-curve trip characteristic. The 78.5 mm depth leaves clearance under most consumer-unit covers without forcing a deeper enclosure. Rated 63 A at 30 °C with a 6 kA breaking capacity at 400 V AC (Icn per EN/IEC 60898-1), this MCB handles the full load current of a 3-phase submain or a large fixed load like a commercial kitchen or HVAC unit.
Termination and wiring
The neutral is on the left (fixed position), which matters when pre-wiring a distribution board with a common neutral bar — verify the busbar orientation before terminating.
Environmental and mechanical ratings
IP20 finger-safe terminals suit installation inside a locked enclosure or distribution board.