Skip to main content
Schneider Electric A9KF71102BQ — 1-Pole MCB (DIN Rail)

A9KF71102BQ Acti9 K60H MCB, 2 A, C Curve, 10 kA, 1P

MPNA9KF71102BQ
Active

Schneider Electric Acti9 K60H miniature circuit-breaker, A9KF71102BQ, 2 A rated current, C curve, 10 kA breaking capacity at 240 V AC, 1P, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9KF71102BQ — Identification
ParameterValue
Product nameActi9 K60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameK60H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9KF71102BQ — Electrical & Protection
ParameterValue
Rated current (In)2 A
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9KF71102BQ — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth70 mm
Tightening torque (by circuit)2 N.m top or bottom
A9KF71102BQ — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9KF71102BQ — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9KF71102BQ — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV

Product details

The A9KF71102BQ is a Schneider Electric Acti9 K60H miniature circuit-breaker, 1 pole, rated 2 A with a C curve and a 10 kA breaking capacity at 240 V AC per EN/IEC 60898-1. Thermal-magnetic trip unit, magnetic trip threshold 5 to 10 times In. Snaps onto DIN rail, 18 mm wide — fits a standard 2-module slot in a distribution board.

The C curve means the magnetic trip activates between 5 and 10 times the rated current — so for a 2 A breaker, instantaneous trip starts at 10 A and is guaranteed by 20 A.

Mounts on DIN rail, fixed position. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible copper; tighten to 2 N·m. Wire strip length 14 mm. The toggle actuator gives clear visual indication of tripped vs on/off state. IP20 finger-safe front, suitable for enclosed distribution boards.

Frequently asked questions

Where can I buy A9KF71102BQ?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm response.

What is the breaking capacity of A9KF71102BQ?

10,000 A Icn at 240 V AC, 50/60 Hz, certified to EN/IEC 60898-1. That is the maximum fault current the breaker can safely interrupt under standard conditions.

What compliance documentation does Schneider provide for A9KF71102BQ?

The breaker is certified to EN/IEC 60898-1, carries IP20 per IEC 60529, and meets tropicalisation class 2 per IEC 60068-1. RoHS and REACH declarations are standard for the Acti9 range; specific documentation is available on request.

MPN