Schneider Electric A9KF71103BQ — 1-Pole MCB (DIN Rail)

Schneider Electric A9KF71103BQ Acti9 K60 MCB, 3 A, C-Curve,

MPNA9KF71103BQ
Active

Schneider Electric Acti9 K60, A9KF71103BQ, miniature circuit breaker, 1P, 3 A, C-curve, 10 kA Icn at 240 V AC, DIN rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9KF71103BQ — Identification
ParameterValue
Product nameActi9 K60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameK60H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9KF71103BQ — Electrical & Protection
ParameterValue
Rated current (In)3 A
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9KF71103BQ — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth70 mm
Tightening torque (by circuit)2 N.m top or bottom
A9KF71103BQ — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9KF71103BQ — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9KF71103BQ — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV

Product details

The Schneider Electric A9KF71103BQ is a 1-pole Acti9 K60 miniature circuit breaker rated 3 A with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In).

The 3 A C-curve is sized for lighting, control transformers, or small resistive loads where the inrush is moderate. Thermal-magnetic trip technology means the bimetal handles sustained overloads and the solenoid clears short-circuits — no electronics to fail. That's one of the narrowest footprints for a single-pole MCB, so it packs tight in a crowded enclosure. Tighten to 2 N·m. IP20 finger protection is standard for a panel-mounted breaker — no special handling needed inside a closed enclosure. Pollution degree 2 covers normal factory-floor conditions with non-conductive contamination. Operating altitude up to 2000 m and 95% relative humidity at 55 °C with tropicalisation class 2 per IEC 60068-1 mean it holds up in hot, humid environments without derating surprises.

Frequently asked questions

What is the breaking capacity of the A9KF71103BQ?

It is rated 10,000 A Icn at 240 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That's the standard fault-interruption rating for a household or light-commercial distribution board.

What wire sizes does the A9KF71103BQ accept?

The tunnel terminals accept 1–25 mm² rigid and 1–16 mm² flexible on both upstream and downstream sides. Strip length is 14 mm, tightening torque 2 N·m.

Where can I buy the A9KF71103BQ and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no fixed stock or price is published here.

MPN