Skip to main content
Schneider Electric A9KF71110BQ — 1-Pole MCB (DIN Rail)

Schneider Electric A9KF71110BQ Acti9 K60 MCB, 10 A, 1P, C Cu

MPNA9KF71110BQ
Active

Schneider Electric Acti9 K60, miniature circuit-breaker, 1P, 10 A, C curve, 10 kA Icn at 240 V AC, DIN rail mount, EN/IEC 60898-1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9KF71110BQ — Identification
ParameterValue
Product nameActi9 K60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameK60H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9KF71110BQ — Electrical & Protection
ParameterValue
Rated current (In)10 A
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9KF71110BQ — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth70 mm
Tightening torque (by circuit)2 N.m top or bottom
A9KF71110BQ — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9KF71110BQ — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9KF71110BQ — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV

Product details

The Schneider Electric A9KF71110BQ is an Acti9 K60 miniature circuit-breaker rated 10 A, single-pole, with a C-curve trip characteristic and a 10 kA Icn breaking capacity at 240 V AC (EN/IEC 60898-1). It is a thermal-magnetic MCB for distribution boards — the C curve means it trips magnetically between 5 and 10 times rated current (50–100 A), so it handles moderate inrush from lighting or small motor loads without nuisance tripping.

At 18 mm width (2 x 9 mm pitches), it occupies a single module slot — no extra space needed for neutral switching since this is a 1P breaker protecting only the phase. Tunnel terminals accept up to 25 mm² rigid or 16 mm² flexible conductors; tightening torque is 2 N.m top or bottom. The IP20 finger-safe terminals are fine for enclosed distribution boards.

Frequently asked questions

Where can I buy A9KF71110BQ and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is A9KF71110BQ's listed depth (70 mm) on this component line?

The depth is 70 mm, which is standard for a single-module Acti9 K60 MCB — it fits flush in a distribution board without protruding past the DIN rail.

What is A9KF71110BQ's listed range (Acti9) on this component line?

The range is Acti9, Schneider Electric's platform for miniature circuit-breakers, residual-current devices, and distribution accessories used in commercial and residential panels.

MPN
A9KF71110BQ