The A9KF71325BQ: Mounts on a standard DIN rail — 6 module pitches (54 mm wide) — and accepts rigid conductors up to 25 mm² or flexible up to 16 mm² in tunnel terminals. IP20 rated, so it's for inside a panel, not exposed.

Schneider Electric A9KF71325BQ Acti9 K60 MCB, 25 A, C-Curve,
Schneider Electric Acti9 K60 miniature circuit breaker, 3-pole, 25 A, C-curve, 10 kA breaking capacity at 415 V AC, DIN rail mount, IP20.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Miniature circuit-breaker |
| Product name | Acti9 K60 |
| Product range | Acti9 |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Network type (AC/DC) | AC |
| Rated current [In] | 25 A |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz |
| Rated impulse withstand voltage [Uimp] | 4 kV |
| Network frequency | 50/60 Hz |
| Poles description | 3P |
| Magnetic tripping limit | 5...10 x In |
| Parameter | Value |
|---|---|
| Breaking capacity | 10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Rated service breaking capacity [Ics] | 7500 A 75 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60898-1 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Local signalling | Without |
| Contact position indicator | No |
| Parameter | Value |
|---|---|
| Connections / terminals | Tunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible |
| Device short name | K60H |
| Control type | Toggle |
| Mounting mode | Fixed |
| Mounting support | DIN rail |
| Usable 9 mm pitches | 6 |
| Width | 54 mm |
| Height | 81 mm |
| Depth | 70 mm |
| Colour | White |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 2 |
| Operating ambient air temperature | -5...55 °C |
| Storage ambient air temperature | -25...85 °C |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60898-1 |
| Parameter | Value |
|---|---|
| Curve code | C |
| Number of protected poles | 3 |
Product details
Frequently asked questions
Where can I buy A9KF71325BQ and how do I get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What is the closest pin-compatible alternative to A9KF71325BQ in this component family?
Within the Acti9 range, the K60 series shares the same physical footprint and DIN-rail mounting. The key difference is the curve code and rated current — the A9KF71325BQ is a 25 A, C-curve. A B-curve variant would trip faster on inrush, while a D-curve handles higher surge loads. No direct pin-compatible substitute outside the family is listed.
What is A9KF71325BQ's listed depth (70 mm) on this component line?
The depth is 70 mm, with a height of 81 mm and width of 54 mm (6 module pitches).
What compliance documentation does this brand provide for A9KF71325BQ (RoHS, REACH, UL, IEC)?
The breaker is certified to EN/IEC 60898-1 and carries IP20 per IEC 60529. It is suitable for isolation per the same standard. The evidence does not list RoHS, REACH, or UL marks specifically, but Schneider typically provides these on request for Acti9 products.