Skip to main content
Schneider Electric A9KR15463 — Residual Current Breakers (RCCB/RCBO)

A9KR15463 Acti9 ID K RCCB, 63 A, 100 mA, 4P, Type AC

MPNA9KR15463
Active

Schneider Electric Acti9 ID K, 4P RCCB, 63 A, 100 mA sensitivity, Type AC, DIN rail clip-on, 380-415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9KR15463 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9KR15463 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemGroup incomer
Electrical durabilityAC-1: 4000 cycles
Mechanical durability (operating cycles)5000 cycles
A9KR15463 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9KR15463 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height81 mm
Depth68 mm
A9KR15463 — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9KR15463 — Approvals
ParameterValue
StandardsEN/IEC 61008-1

Product details

The Schneider Electric A9KR15463 is an Acti9 ID K residual current circuit breaker — a 4-pole, 63 A, 100 mA sensitivity Type AC RCCB for 380-415 V AC 50 Hz networks.

Mounts on standard DIN rail via clip-on tabs — no tools needed for the rail, just a screwdriver for the terminals. The 72 mm wide body fits an 8-module pitch on the rail.

Rated breaking and making capacity Idm 630 A / Im 630 A. Insulation voltage rated 440 V AC. Instantaneous tripping with voltage-independent residual current technology — no auxiliary supply needed to detect earth faults. Complies with EN/IEC 61008-1, pollution degree 2, IP20 (IP40 in modular enclosure). Storage range -25 to 85 °C, operating range -5 to 55 °C.

Frequently asked questions

Who supplies A9KR15463 and how is it quoted for volume purchases?

Sourced through independent distribution channels. Submit an RFQ for volume pricing and availability; confirmed at quote time.

What is A9KR15463's earth-leakage sensitivity and type?

100 mA sensitivity, Type AC — detects sinusoidal AC residual currents only, no time delay (instantaneous).

What compliance documentation does this brand provide for A9KR15463?

The RCCB is certified to EN/IEC 61008-1, with IP20/IP40 protection and tropicalisation class 2 per IEC 60068-1.

MPN
A9KR15463