Skip to main content
Schneider Electric A9L08400 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9L08400 Acti9 iPRD8 Surge Arrester, 4P,

MPNA9L08400
Active

Schneider Electric Acti9 iPRD8, Type 2+3 surge arrester, 4 poles, 350 V continuous, 8 kA max discharge, clip-on DIN rail, white (RAL 9003).

$134.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L08400 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)230/400 V AC (+/- 10 %) at 50/60 Hz
Poles description4P
A9L08400 — Identification
ParameterValue
Product nameActi9 iPRD
Product / component typeSurge arrester with pluggable cartridge
Device short nameiPRD8
A9L08400 — Mechanical
ParameterValue
Mounting modeClip-on (DIN rail)
Width in 9 mm modules8
Terminal connectionsTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Terminal tightening torque2.5 N.m
Width72 mm
Height85 mm
Depth69 mm
A9L08400 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
Relative humidity5...95 %
Operating altitude2000 m
A9L08400 — Approvals
ParameterValue
StandardsEN 61643-11:2012 IEC 61643-11:2011

Product details

The Schneider Electric A9L08400 is an Acti9 iPRD8 modular surge arrester — a Type 2 + 3 device combining MOV and GDT technology for the electrical distribution network. It protects TN-C-S systems at 230/400 V AC (+/- 10 %), 50/60 Hz. The 4-pole configuration covers, L2, L3, and N with common-mode protection. Rated for a nominal discharge current of 2.5 kA per mode (L/PE and N/PE) and a maximum discharge current of 8 kA. The voltage protection level stays under 1.2 kV for Type 3 common mode L/PE. That means it clamps fast enough to protect downstream electronics from the bulk of a surge event.

Clip-on DIN rail mount, 8 x 9 mm pitches wide. Dimensions: 85 mm high, 72 mm wide, 69 mm deep. Tunnel-type terminals top and bottom accept 2.5 to 35 mm² conductors; tighten to 2.5 N·m. The white (RAL 9003) housing blends into standard distribution board layouts. Relative humidity 5 to 95 %. Rated for operation up to 2000 m altitude. IK03 impact protection per IEC 62262 — adequate for enclosed panel mounting where accidental tool contact is the main risk.

Backup protection and coordination

This surge arrester requires an upstream overcurrent protective device. Schneider specifies several options: an iC60L 10 A curve C (Icu 25 kA), iC60N 10 A curve C (Icu 10 kA), iC60H 10 A curve C (Icu 15 kA), or fuses gG 25 A (Icu 15 kA) or gG 80 A (Icu 50 kA). Temporary overvoltage withstand: 337 V L/N for 5 seconds, and 1200 V N/PE for 200 ms in safe failure mode. The ground residual current is 0.003 mA under normal conditions, rising to 0.6 mA in fault — well below thresholds that would nuisance-trip an RCD.

Compliant with EN 61643-11:2012 and IEC 61643-11:2011. Carries KEMA-KEUR and NF quality labels.

Frequently asked questions

What backup overcurrent protection does the A9L08400 require?

The A9L08400 requires an upstream overcurrent protective device. Acceptable options include iC60L, iC60N, or iC60H circuit breakers at 10 A curve C, or gG fuses rated 25 A or 80 A, depending on the available fault current.

What are the key electrical ratings of the A9L08400?

Rated operational voltage 230/400 V AC, maximum continuous operating voltage 260 V N/PE and 350 V L/PE, nominal discharge current 2.5 kA, maximum discharge current 8 kA, and voltage protection level under 1.2 kV for Type 3 common mode L/PE.

What compliance documentation does Schneider provide for the A9L08400?

The A9L08400 is certified to EN 61643-11:2012 and IEC 61643-11:2011, and carries KEMA-KEUR and NF quality labels. RoHS and REACH declarations are standard for the Acti9 line and available with order documentation.

MPN
A9L08400