Skip to main content
Schneider Electric A9L15585 — Surge Protection Devices (SPD)

Schneider Electric A9L15585 Acti9 iPF65r Surge Arrester, 4P,

MPNA9L15585
Obsolete

Schneider Electric Acti9 iPF, Type 2 surge arrester, 4P, 340 V continuous, 65 kA max discharge, with remote signalling, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L15585 — Identification
ParameterValue
Product nameActi9 iPF
Product/component typeSurge arrester
Product rangeActi9
Compatibility codeIPF65r
Device applicationDistribution
A9L15585 — Protection ratings
ParameterValue
SPD class/typeType 2
Max. continuous operating voltage (Uc)Common mode: 340 V L/PE Common mode: 340 V N/PE
Voltage protection level (Up)Common mode Common mode <1.5 kV type 2 N/PE
Nominal discharge current (In)Common mode: 20 kA (L/PE) Common mode: 20 kA (N/PE)
Max. discharge current (Imax)Common mode: 65 kA L/PE Common mode: 65 kA N/PE
Total discharge current (Itotal)260 kA
Surge arrester technologyMOV
Surge arrester typeElectrical distribution network
A9L15585 — Electrical
ParameterValue
Rated operational voltage (Ue)230/400 V AC (+/- 10 %) at 50/60 Hz
Pole configuration4P
Earthing systemTN-C
Associated disconnector device typeAssociated circuit breaker IC60N 50 A curve C - Icu 10 kA Associated circuit breaker iC60H 50 A curve C - Icu 15 kA Associated circuit breaker NG125N 50 A curve C - Icu 25 kA Associated circuit breaker NG125H 50 A curve C - Icu 36 kA Associated circuit breaker NG125L 50 A curve C - Icu 50 kA
A9L15585 — Signalling
ParameterValue
Remote signallingWith
Signal contact configuration1 SD (1 C/O)
Signalling circuit rating0.25 A/250 V AC 50/60 Hz
A9L15585 — Approvals
ParameterValue
StandardsEN 61643-11 IEC 61643-11
Quality labels / certificationsKEMA-KEUR NF OVE
A9L15585 — Mechanical
ParameterValue
Terminal connectionsTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Mounting modeClip-on (DIN rail)
Width72 mm
Height81.4 mm
Depth69 mm
9 mm pitch units8
Terminal tightening torque2.5 N.m
ColourWhite (RAL 9003)
A9L15585 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Relative humidity5...90 %
Storage ambient temperature-40...85 °C
Impact protection (IK)IK03 conforming to IEC 62262
Operating altitude2000 m

Product details

The Schneider Electric A9L15585 is a Type 2 surge arrester from the Acti9 iPF range, designated iPF65r. It is a 4-pole MOV-based unit rated for 230/400 V AC (+/- 10 %) at 50/60 Hz, with a maximum continuous operating voltage of 340 V L/PE and N/PE. The nominal discharge current is 20 kA per mode (L/PE, N/PE), and the maximum discharge current reaches 65 kA per mode, with a total [I total] discharge current of 260 kA. The voltage protection level [Up] is <1.5 kV for common mode (N/PE). This unit includes a remote signalling contact (1 SD, 1 C/O) rated at 0.25 A / 250 V AC.

Depth is 69 mm, height is 81.4 mm. Terminals are tunnel type, accepting 2.5 to 35 mm² on both upside and downside. Tightening torque is 2.5 N·m. The housing is white (RAL 9003) with an IK03 impact rating per IEC 62262.

The A9L15585 is designed and tested to EN 61643-11 and IEC 61643-11. It carries quality labels KEMA-KEUR, NF, and OVE. The device is rated for TN-C earthing systems. Relative humidity tolerance is 5 to 90 %. Maximum operating altitude is 2000 m.

Frequently asked questions

Who supplies A9L15585 and how is it quoted for volume purchases?

The A9L15585 is sourced through independent distribution channels and is quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quote.

What is A9L15585's listed depth and width?

The depth is 69 mm and the width is 72 mm (8 modules of 9 mm pitch).

What compliance documentation does this brand provide for A9L15585?

The A9L15585 is tested to EN 61643-11 and IEC 61643-11, and carries KEMA-KEUR, NF, and OVE quality labels. It is rated for TN-C earthing systems.

MPN
A9L15585