Specifications

A9L15587 — Identification
ParameterValue
Product nameActi9 iPF
Product rangeActi9
Device short nameiPF
Product / component typeSurge arrester
Device applicationDistribution
A9L15587 — Electrical
ParameterValue
Pole configuration2P
Rated operational voltage [Ue]230 V AC (+/- 10 %) at 50/60 Hz
A9L15587 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81.4 mm
Depth69 mm
Mounting modeClip-on (DIN rail)
Terminal connectionsTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Terminal tightening torque2.5 N.m
A9L15587 — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...85 °C
Relative humidity5...90 %
A9L15587 — Approvals
ParameterValue
Standards / complianceEN 61643-11 IEC 61643-11

Product details

The Schneider Electric A9L15587 is an Acti9 iPF40 Type 2 surge arrester, a 2-pole MOV-based unit rated for 230 V AC (+/- 10 %) at 50/60 Hz with a maximum continuous operating voltage of 340 V common mode.

The nominal discharge current is 15 kA per mode (L/PE and N/PE), and the maximum discharge current reaches 40 kA per mode. Total discharge current across all paths sums to 80 kA. These figures define the surge capacity: 15 kA is the sustained rating for repeated events, while 40 kA is the single-event survival limit. The protection level Up is clamped below 1.5 kV common mode, which keeps let-through voltage within the impulse withstand of downstream equipment rated for 1.5 kV or higher. The unit is designed for TN-C systems only — the earthing arrangement is fixed, so verify your network configuration before specifying. It requires an associated circuit breaker upstream; the manufacturer lists iC60N, iC60H, or iC60L at 40 A curve C with interrupting capacities from 10 kA to 25 kA depending on the breaker variant. Terminals accept 2.5 to 35 mm² conductors on both top and bottom, tunnel type, with a tightening torque of 2.5 N.m. The housing is white (RAL 9003), rated IK03 for mechanical impact, and occupies 4 x 9 mm pitches (36 mm width) on the DIN rail.

The surge arrester complies with EN 61643-11 and IEC 61643-11, the governing standards for low-voltage surge protective devices. Quality marks include OVE (Austria), KEMA-KEUR (Netherlands), and NF (France). Operating temperature range is -25 to 60 °C, storage from -40 to 85 °C, with relative humidity 5 to 90 % and maximum operating altitude 2000 m.

Frequently asked questions

Where can I buy A9L15587 and how do I get a price?

We source the A9L15587 to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time.

What compliance documentation does this brand provide for A9L15587?

The A9L15587 carries EN 61643-11 and IEC 61643-11 compliance, plus quality marks OVE, KEMA-KEUR, and NF. Documentation typically includes the declaration of conformity and test certificates per those standards.

What is the closest alternative to A9L15587 in the Acti9 family?

Within the Acti9 iPF range, the current-production successor would be a functionally similar Type 2 SPD with the same pole count and voltage rating. Verify the exact order code with your Schneider Electric contact or distributor for a drop-in replacement that matches the 2-pole, 340 V, 40 kA specification.