Skip to main content
Schneider Electric A9L16555 — 1-Pole MCB (DIN Rail)

Schneider Electric A9L16555 Acti9 iPRD65r Surge Arrester, 1P

MPNA9L16555
Obsolete

Schneider Electric Acti9 iPRD65r, Type 2 surge arrester, 1 pole, 460 V, 65 kA discharge, with remote signalling, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L16555 — Identification
ParameterValue
Product nameActi9 iPRD
Product / component typeSurge arrester with pluggable cartridge
Device short nameiPRD65r
Poles description1P
Device applicationDistribution
A9L16555 — Electrical & Protection
ParameterValue
Rated operational voltage (Ue)230 V AC (+/- 10 %) at 50/60 Hz
A9L16555 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Mounting modeClip-on (DIN rail)
Width18 mm
Height81 mm
Depth69 mm
Tightening torque (by circuit)2.5 N.m
A9L16555 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
A9L16555 — Approvals
ParameterValue
Conformity standardsEN 61643-11 IEC 61643-11

Product details

The Schneider Electric A9L16555 is an Acti9 iPRD65r Type 2 surge arrester — a 1-pole MOV-based unit rated for 460 V continuous operation (L/PE) on IT earthing systems. Its headline numbers: 65 kA maximum discharge current (common mode L/PE), 20 kA nominal discharge current, and a voltage protection level below 2 kV. That puts it squarely in Type 2 SPD territory for distribution boards — sized for main or sub-distribution panels where lightning-induced surges need clamping before they reach downstream electronics.

This part is obsolete per the manufacturer's lifecycle status.

Mounts via clip-on to DIN rail. Tunnel-type terminals top and bottom accept 2.5 to 35 mm² conductors; tighten to 2.5 N·m. The remote signalling contact (1 C/O, rated 0.25 A / 250 V AC) lets a PLC or panel indicator monitor arrester status without opening the enclosure. Complies with EN 61643-11 and IEC 61643-11.

Frequently asked questions

Where can I buy A9L16555 and get a price?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent supply network.

What standards does A9L16555 comply with?

It complies with EN 61643-11 and IEC 61643-11 for Type 2 surge protective devices.

What is the width of A9L16555?

18 mm, which is 2 standard 9 mm DIN-rail pitches.

MPN
A9L16555