Skip to main content
Schneider Electric A9L16672 — 1-Pole MCB (DIN Rail)

Schneider Electric A9L16672 Acti9 iPRD Surge Arrester, Type

MPNA9L16672
Obsolete

Schneider Electric Acti9 iPRD Type 2 surge arrester, 1P+N, 340 V, 20 kA max discharge, with remote signalling, clip-on DIN rail, white (RAL 9003).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L16672 — Identification
ParameterValue
Product nameActi9 iPRD
Product / component typeSurge arrester with pluggable cartridge
Device short nameiPRD
Poles description1P + N
Device applicationDistribution
A9L16672 — Electrical & Protection
ParameterValue
Rated operational voltage (Ue)230 V AC (+/- 10 %) at 50/60 Hz
A9L16672 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Mounting modeClip-on (DIN rail)
Width36 mm
Height81 mm
Depth69 mm
Tightening torque (by circuit)2.5 N.m
A9L16672 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
A9L16672 — Approvals
ParameterValue
Conformity standardsEN 61643-11 IEC 61643-11

Product details

The Schneider Electric A9L16672 is an Acti9 iPRD20r modular surge arrester — Type 2, 1P+N, rated for 230 V AC (+/- 10 %) at 50/60 Hz. The MOV + GDT technology handles common-mode and differential-mode surges up to 20 kA maximum discharge current, with a voltage protection level below 1.4 kV (type 2 N/PE).

The 20 kA maximum discharge current (common mode L/PE, N/PE, and differential mode L/N) tells you this arrester can safely divert a direct lightning-induced surge at the service entrance of a small commercial building — it is not a fine-protection device for sensitive electronics downstream. The nominal discharge current is 5 kA per mode, which is the standard test current for Type 2 arresters per EN 61643-11 and IEC 61643-11. The 69 mm depth and 36 mm width (4 x 9 mm pitches) mean it occupies a standard 4-module width on the DIN rail — plan for that slot in your panel layout. The tunnel-type terminals accept 2.5 to 35 mm² conductors on both the line and load sides, which covers most incoming supply cables in a small commercial panel. Tightening torque is 2.5 N.m.

The A9L16672 carries quality labels OVE, NF, and KEMA-KEUR, and is certified to EN 61643-11 and IEC 61643-11. The remote signalling contact (1 C/O, rated 0.25 A / 250 V AC) allows a panel PLC or alarm system to monitor arrester status — useful for maintenance planning in an unattended site.

Frequently asked questions

Where can I buy A9L16672 and how do I get a price?

We source this part to order against an RFQ. Submit a request for quote; availability and current pricing are confirmed at quote time through our independent distribution network.

What is A9L16672's listed depth (69 mm) on this component line?

The depth is 69 mm, width 36 mm, height 81 mm — a 4-module DIN-rail footprint.

What compliance documentation does this brand provide for A9L16672?

The part is certified to EN 61643-11 and IEC 61643-11, and carries OVE, NF, and KEMA-KEUR quality labels. Standard Schneider Electric documentation (declaration of conformity, technical data sheet) is available on request.

MPN