Skip to main content
Schneider Electric A9L20300 — Residual Current Breakers (RCCB/RCBO)

A9L20300 Acti9 iPRD20 Type 2 Surge Arrester, 3P 350V

MPNA9L20300
Active

Schneider Electric Acti9 iPRD20, Type 2 surge arrester, 3P, 400 V AC, 20 kA max discharge, pluggable cartridge, clip-on DIN rail.

$120.95Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L20300 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)400 V AC (+/- 10 %) at 50/60 Hz
Poles description3P
A9L20300 — Identification
ParameterValue
Product nameActi9 iPRD
Product / component typeSurge arrester with pluggable cartridge
Device short nameiPRD20
A9L20300 — Mechanical
ParameterValue
Mounting modeClip-on (DIN rail)
Width in 9 mm modules6
Terminal connectionsTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Terminal tightening torque2.5 N.m
Width54 mm
Height85 mm
Depth69 mm
A9L20300 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
Relative humidity5...95 %
Operating altitude2000 m
A9L20300 — Approvals
ParameterValue
StandardsEN 61643-11:2012 IEC 61643-11:2011

Product details

Type 2 surge protection for distribution panels

The Schneider Electric A9L20300 is an Acti9 iPRD20 Type 2 surge arrester with pluggable cartridges, designed for 3-phase distribution networks at 400 V AC (+/- 10 %) 50/60 Hz. The MOV + GDT technology handles a nominal discharge current of 5 kA per mode and a maximum discharge current of 20 kA in common and differential modes, with a voltage protection level below 1.4 kV.

The 20 kA Imax (maximum discharge current) tells you this arrester can safely divert a single high-energy surge up to that level without failing — critical for main distribution boards in areas with moderate lightning exposure. The 5 kA In (nominal discharge current) is the rating that defines its Type 2 classification per IEC 61643-11:2011; it's the current the arrester can withstand 20 times without degradation. The 350 V Uc (maximum continuous operating voltage) means it's rated for 400 V TN or IT systems, and the 337 V temporary overvoltage withstand for 5 seconds handles typical grid faults without needing a backup disconnector.

Mounts via clip-on DIN rail — standard for Acti9 enclosures. Tunnel-type terminals on both top and bottom accept 2.5 to 35 mm² conductors, tightened to 2.5 N.m. The 85 mm height and 69 mm depth fit standard 2-row enclosures. The white RAL 9003 housing carries IK03 impact resistance per IEC 62262, adequate for panel environments. The disconnector options listed include associated circuit breakers (iC60N/H/L or NG125H/L, 20 A curve C) or gG fuses up to 80 A — the back-up protection must be coordinated per the manufacturer's table.

Frequently asked questions

What is the maximum discharge current of A9L20300?

The maximum discharge current (Imax) is 20 kA in common mode (L/PE, N/PE) and 20 kA in differential mode (L/N). The nominal discharge current (In) is 5 kA per mode.

What back-up protection is required for A9L20300?

The disconnector options include associated circuit breakers iC60N/H/L 20 A curve C (Icu 10/15/25 kA), NG125H/L 20 A curve C (Icu 36/50 kA), or gG fuses 40 A (Icu 15 kA) and 80 A (Icu 50 kA). The back-up protection must be selected per the manufacturer's coordination table.

Where can I buy A9L20300 and get current pricing?

The A9L20300 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
A9L20300