Skip to main content
Schneider Electric A9L40300 — Residual Current Breakers (RCCB/RCBO)

A9L40300 Acti9 iPRD40 Type 2 Surge Arrester, 3P, 40 kA

MPNA9L40300
Active

Schneider Electric Acti9 iPRD40, Type 2 surge arrester, 3P, 350 V Uc, 40 kA Imax, 15 kA In, pluggable cartridge, clip-on DIN rail.

$133.24Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L40300 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)400 V AC (+/- 10 %) at 50/60 Hz
Poles description3P
A9L40300 — Identification
ParameterValue
Product nameActi9 iPRD
Product / component typeSurge arrester with pluggable cartridge
Device short nameiPRD40
A9L40300 — Mechanical
ParameterValue
Mounting modeClip-on (DIN rail)
Width in 9 mm modules6
Terminal connectionsTunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²
Terminal tightening torque2.5 N.m
Width54 mm
Height85 mm
Depth69 mm
A9L40300 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
Relative humidity5...95 %
Operating altitude2000 m
A9L40300 — Approvals
ParameterValue
StandardsEN 61643-11:2012 IEC 61643-11:2011

Product details

The A9L40300 is a Type 2 surge arrester from the Acti9 iPRD40 range, designed for 3-phase distribution boards. The 40 kA maximum discharge current (Imax) per L/PE path means it can safely divert a single high-energy surge from a nearby lightning strike; the 15 kA nominal discharge current (In) is the sustained rating it handles repeatedly without degrading. The 350 V Uc continuous operating voltage matches 400 V AC (+/-10%) TN-C and IT 230 V earthing systems — common in European commercial and light industrial panels. The pluggable cartridge lets a panel OEM or MRO planner swap the MOV module without pulling the base wiring, which keeps line-down time under a minute.

The housing is 54 mm wide — three 18 mm modular pitches — and 85 mm tall, 69 mm deep. That puts it in a standard 3-module slot on any DIN-rail enclosure. The tunnel terminals accept 2.5 to 35 mm² on both top and bottom, so it handles incoming mains tails as well as downstream distribution wiring. Tightening torque is 2.5 N.m, typical for a 35 mm² clamp. The white RAL 9003 colour matches the rest of the Acti9 family, which keeps a uniform look in a panel that a quality doc controller or inspector might photograph for the FAT record.

Associated disconnector and coordination

Schneider specifies associated circuit breakers and fuses for the iPRD40. The list includes the iC60H (40 A, curve C, 15 kA Icu), iC60N (40 A, 10 kA), and gG fuses up to 80 A.

Frequently asked questions

What is the A9L40300 used for?

The A9L40300 is a Type 2 surge arrester used to protect 3-phase distribution boards in commercial and light industrial installations. It clamps transient overvoltages from switching operations or indirect lightning strikes to below 1.4 kV (Up) per L/PE path.

Where can I buy the A9L40300?

The A9L40300 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
A9L40300