A9MEM1564 — Identification
ParameterValue
Product / component typeEnergy sensor
Product namePowerTag A9 F63
Range of productPowerLogic
A9MEM1564 — Electrical
ParameterValue
Network frequency50 Hz 60 Hz
A9MEM1564 — Mechanical
ParameterValue
Mounting modeBy screws (terminals)
Mounting supportOn circuit breaker
WidthSensor element: 18 mm
HeightSensor element: 20 mm
DepthSensor element: 44.5 mm
ColourWhite (RAL 9003)
A9MEM1564 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05
Pollution degree3
Operating ambient air temperature-25...60 °C
Storage ambient air temperature-40...85 °C
A9MEM1564 — Approvals
ParameterValue
StandardsIEC 61557-12 IEC 61010-1 IEC 61010-2-030 IEC 61326-1 ETSI EN 300 328 ETSI EN 301 489-1

Product details

Mounts on the top or bottom of a compatible circuit breaker via screw terminals, with a 0.25 m flying lead terminated in a 1 x 0.33 mm² cable. The sensor element measures 44.5 mm deep by 18 mm wide by 20 mm high — compact enough to fit in a crowded DIN-rail enclosure without blocking adjacent breaker toggles. Rated IP20 with IK05 impact protection, so it's suited for dry indoor switchboard environments where accidental tool contact is the main risk.

The 63 A maximum current (Imax) and 130 A saturation current define the measurement range: the sensor stays linear up to 63 A and can survive short-duration overloads up to 130 A without damage. Supply voltage is 100...125 V AC ±20 %, 50/60 Hz, drawing a starting current of 40 mA and a maximum power consumption of 1 VA — negligible load on the control transformer.

Carries CE marking under the Radio Equipment Directive 2014/53/EU and complies with IEC 61557-12, IEC 61010-1, IEC 61010-2-030, IEC 61326-1, ETSI EN 300 328, and ETSI EN 301 489-1 — covers both measurement accuracy and wireless coexistence. Rated for operating altitude up to 2000 m and relative humidity 0...95 % at 45 °C per IEC 60721-3-3, with vibration resistance 3M4.

Frequently asked questions

What is A9MEM1564's maximum current rating?

The A9MEM1564 has a maximum current (Imax) of 63 A, with a saturation current of 130 A for short-duration overloads.

What compliance documentation does Schneider provide for A9MEM1564?

The A9MEM1564 carries CE marking under the Radio Equipment Directive 2014/53/EU and complies with IEC 61557-12, IEC 61010-1, IEC 61010-2-030, IEC 61326-1, ETSI EN 300 328, and ETSI EN 301 489-1.

What is A9MEM1564's accuracy class for energy measurement?

The A9MEM1564 achieves Class 1 for current, active power, and active energy, and Class 0.5 for voltage, all per IEC 61557-12.

MPN