Schneider Electric A9N16204 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N16204 Acti9 xID RCCB, 2P 40A 30mA Type

MPNA9N16204
Active

Schneider Electric Acti9 xID RCCB, 2P, 40 A, 30 mA Type AC, 230-240 V AC, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N16204 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Local signalling / indicationON, OFF, fault trip
A9N16204 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durability4000 cycles
Mechanical durability (operating cycles)4000 cycles
A9N16204 — Identification
ParameterValue
Product nameActi9 xID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short namexID
A9N16204 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth75 mm
A9N16204 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N16204 — Approvals
ParameterValue
StandardsEN 61008-2-1 IEC 61008-2-1 EN/IEC 61008-1

Product details

The Schneider Electric A9N16204 is an Acti9 xID residual current circuit breaker (RCCB) — a 2-pole, 40 A, 30 mA sensitivity Type AC device for 230-240 V AC 50 Hz networks. The 30 mA earth-leakage threshold is the standard for personal protection against indirect contact in residential and commercial final circuits; Type AC detection covers sinusoidal AC residual currents only.

Neutral is on the left. The IP20 enclosure suits clean, dry indoor panels.

Compliant with EN/IEC 61008-1 and EN/IEC 61008-2-1. Pollution degree 2. Storage temperature range -40 to 85 °C. Rated insulation voltage 500 V AC. Breaking and making capacity 500 A per IEC 61008-1. Electrical and mechanical durability each 4000 cycles.

Frequently asked questions

Where can I buy A9N16204?

It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of A9N16204?

It is a 2-pole RCCB rated 40 A, 30 mA sensitivity Type AC, for 230-240 V AC 50 Hz, with a breaking capacity of 500 A per IEC 61008-1.

What is the mounting and connection spec for A9N16204?

Clip-on DIN rail mount, 36 mm wide (4 x 9 mm pitches). Tunnel terminals accept 1-35 mm² rigid or 1-25 mm² flexible, strip length 14 mm, torque 3.5 N·m. Neutral left, IP20.

MPN
A9N16204