Skip to main content
Schneider Electric A9N16208 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N16208 Acti9 xID RCCB, 63 A, 30 mA, Typ

MPNA9N16208
Active

Schneider Electric Acti9 xID RCCB, 2P, 63 A, 30 mA, Type AC, 230-240 V AC, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N16208 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Local signalling / indicationON, OFF, fault trip
A9N16208 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durability4000 cycles
Mechanical durability (operating cycles)4000 cycles
A9N16208 — Identification
ParameterValue
Product nameActi9 xID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short namexID
A9N16208 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth75 mm
A9N16208 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N16208 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 IEC 61008-2-1 EN 61008-2-1

Product details

The breaking and making capacity is 630 A, conforming to EN/IEC 61008-1. This is a Type AC device, meaning it detects sinusoidal AC residual currents only — not pulsed DC or high-frequency components.

The tunnel-type terminals accept 1-35 mm² rigid or 1-25 mm² flexible conductors; wire stripping length is 14 mm. IP20 rated — suitable for installation inside a panel or enclosure where it is protected from contact and dripping water. The toggle control provides ON, OFF, and fault-trip local signalling, and a padlocking device is available for lockout/tagout.

Frequently asked questions

What is A9N16208's rated current and earth-leakage sensitivity?

The A9N16208 is rated at 63 A with a 30 mA earth-leakage sensitivity, Type AC, suitable for sinusoidal AC residual currents.

What standards does the A9N16208 comply with?

It complies with EN/IEC 61008-1 and IEC 61008-2-1, EN 61008-2-1, covering general and functional requirements for RCCBs.

Where can I buy the A9N16208?

The A9N16208 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9N16208