Specifications

A9N16213 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Local signalling / indicationON, OFF, fault trip
A9N16213 — Electrical Ratings
ParameterValue
Rated current (In)80 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durability4000 cycles
Mechanical durability (operating cycles)4000 cycles
A9N16213 — Identification
ParameterValue
Product nameActi9 xID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short namexID
A9N16213 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth75 mm
A9N16213 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N16213 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN 61008-2-1 IEC 61008-2-1

Product details

The Schneider Electric A9N16213 is an Acti9 xID residual current circuit breaker (RCCB) — 2 poles, rated 80 A continuous, with 100 mA earth-leakage sensitivity, Type AC. The 230-240 V AC 50 Hz operational voltage and 800 A breaking capacity per EN/IEC 61008-1 mean it handles standard single-phase residential or light commercial sub-distribution. The instantaneous trip on AC sinusoidal fault currents gives fast disconnection for basic shock protection, but Type AC only detects sinusoidal residual currents — not pulsed DC or smooth DC waveforms that VFDs or switched-mode supplies can generate.

Clip-on mounting to DIN rail, neutral on the left. Tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible on top or bottom — wire stripping length 14 mm, tightening torque 3.5 N·m. The 18 mm phase-to-phase pitch matches standard Acti9 busbar spacing. IP20 rated, so it lives inside an enclosure, not in a washdown zone. Padlocking provision allows lockout/tagout for isolation duty (suitability for isolation is marked).

Meets EN/IEC 61008-1 and EN 61008-2-1. Storage range -40 to 85 °C, 95 % RH at 55 °C. Electrical and mechanical durability both rated at 4000 cycles — consistent with a residential-duty RCCB, not a high-cycling industrial contactor.

Frequently asked questions

Where can I buy the A9N16213?

The A9N16213 is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution.

What is the A9N16213 used for?

It is a 2-pole residual current circuit breaker (RCCB) for AC circuits, rated 80 A with 100 mA earth-leakage sensitivity. It provides disconnection on sinusoidal fault currents in residential or light commercial sub-distribution panels.

What are the key ratings of the A9N16213?

Rated current 80 A, earth-leakage sensitivity 100 mA Type AC, operational voltage 230-240 V AC 50 Hz, breaking capacity 800 A per EN/IEC 61008-1, 2 poles, instantaneous trip.

MPN