Schneider Electric A9N16237 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N16237 Acti9 xID RCCB, 40 A, 30 mA, Typ

MPNA9N16237
Active

Schneider Electric Acti9 xID RCCB, 2P, 40 A, 30 mA, Type A-SI, 230-240 V AC, DIN rail clip-on, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N16237 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Local signalling / indicationON, OFF, fault trip
A9N16237 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durability4000 cycles
Mechanical durability (operating cycles)4000 cycles
A9N16237 — Identification
ParameterValue
Product nameActi9 xID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short namexID
A9N16237 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth75 mm
A9N16237 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N16237 — Approvals
ParameterValue
StandardsEN 61008-2-1 EN/IEC 61008-1 IEC 61008-2-1

Product details

What this RCCB carries

The Schneider Electric A9N16237 is an Acti9 xID residual current circuit breaker (RCCB) — 2-pole, 40 A rated current, 30 mA earth-leakage sensitivity, Type A-SI (Super Immunised). It clips onto a DIN rail, occupies 4 x 9 mm pitches (36 mm wide), and is rated for 230-240 V AC at 50 Hz. The 30 mA trip threshold covers standard personnel protection; the Type A-SI classification means it handles pulsed DC fault currents and is immunised against nuisance tripping from high-frequency leakage (switched-mode supplies, VFDs, LED drivers). Breaking capacity is 500 A per EN/IEC 61008-1.

Clip-on mounting to DIN rail, neutral on the left, tunnel terminals top and bottom — accepts 1-35 mm² rigid or 1-25 mm² flexible. Wire stripping length 14 mm; tightening torque 3.5 N·m. Connection pitch is 18 mm between phases. IP20 finger-safe front, suitable for enclosed distribution boards. Local signalling shows ON, OFF, and fault trip; padlocking provision for lockout/tagout.

Frequently asked questions

How do I get current pricing and availability for A9N16237?

The A9N16237 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is A9N16237's listed depth (75 mm) on this component line?

The A9N16237 has a depth of 75 mm.

What is A9N16237's listed range (Acti9) on this component line?

The A9N16237 belongs to the Schneider Electric Acti9 range, product name Acti9 xID.

What compliance documentation does this brand provide for A9N16237 (RoHS, REACH, UL, IEC)?

The A9N16237 complies with EN 61008-2-1, EN/IEC 61008-1, and IEC 61008-2-1. It is tropicalised per IEC 60068-1 (class 2).

MPN