Skip to main content
Schneider Electric A9N16260 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N16260 Acti9 xID RCCB, 63 A, 300 mA, 4P

MPNA9N16260
Active

Schneider Electric Acti9 xID RCCB, A9N16260, 4P, 63 A, 300 mA Type AC, 400-415 V AC, DIN rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N16260 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Local signalling / indicationON, OFF, fault trip
A9N16260 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)400...415 V AC 50 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durability4000 cycles
Mechanical durability (operating cycles)4000 cycles
A9N16260 — Identification
ParameterValue
Product nameActi9 xID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short namexID
A9N16260 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height81 mm
Depth75 mm
A9N16260 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N16260 — Approvals
ParameterValue
StandardsEN 61008-2-1 IEC 61008-2-1 EN/IEC 61008-1

Product details

The Schneider Electric A9N16260 is an Acti9 xID residual current circuit breaker (RCCB) — a 4-pole, 63 A unit with 300 mA earth-leakage sensitivity, Type AC, rated for 400-415 V AC at 50 Hz.

The 300 mA sensitivity on this RCCB is not for personnel protection — that's the 30 mA job. This is sized for fire prevention and equipment protection on circuits with higher natural leakage, like long cable runs or industrial heaters. Same footprint, different internal sensing.

Mounts on standard DIN rail via the clip-on mechanism. Neutral is on the left (fixed position). Tunnel terminals accept 1-35 mm² rigid or 1-25 mm² flexible cable; strip length is 14 mm, torque to 3.5 N·m. The 72 mm width (8 x 18 mm pitches) is a standard 4P RCCB footprint — it fits any Acti9 board without crowding adjacent ways. Lockable with a padlocking device for lockout/tagout.

Rated breaking and making capacity is 630 A per EN/IEC 61008-1. Insulation voltage is 500 V AC. Pollution degree 2, tropicalisation class 2 per IEC 60068-1 (handles 95% RH at 55 °C). Electrical and mechanical durability are both rated at 4000 cycles. IP20 finger-safe terminals. Ambient storage range is -40 to 85 °C.

Frequently asked questions

How do I get current pricing and availability for the A9N16260?

Submit an RFQ through this listing. Pricing and lead time are confirmed at quote time through independent distribution channels.

What is the closest alternative to the A9N16260 in the Acti9 family?

The closest alternative is the same Acti9 xID RCCB but with a different sensitivity or type — for example, a 30 mA Type A variant for personnel protection on circuits with pulsed DC loads. The mechanical footprint and wiring are identical; only the internal trip coil changes.

What is the A9N16260's depth?

The depth is 75 mm.

What compliance standards does the A9N16260 meet?

It conforms to EN 61008-2-1, IEC 61008-2-1, and EN/IEC 61008-1. Tropicalisation is class 2 per IEC 60068-1. IP20 rated.