Schneider Electric A9N18346 — 2-Pole MCB (DIN Rail)

Schneider Electric A9N18346 Acti9 C120 MCB, 100A B Curve 2P,

MPNA9N18346
Active

Schneider Electric Acti9 C120, miniature circuit breaker, 100 A, B curve, 2P, 10 kA Icn at 400 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N18346 — Identification
ParameterValue
Product nameActi9 C120
Series / familyActi9
Device short nameC120N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N18346 — Electrical
ParameterValue
Rated current [In]100 A at 30 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N18346 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]7500 A 75 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Energy limitation class3 conforming to EN/IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N18346 — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N18346 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N18346 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1 EN/IEC 60947-2

Product details

The Schneider Electric A9N18346 is a 100 A rated miniature circuit breaker from the Acti9 C120 series, 2-pole, B-curve, with a 10 kA Icn breaking capacity at 400 V AC.

Rated 10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. It also carries 10 kA Icu at 220-240 V and 380-415 V AC under the industrial standard. Dual-rated to both the household (60898-1) and industrial (60947-2) standards, so it qualifies for distribution boards and industrial panel applications alike.

Tunnel terminals accept 1-50 mm² rigid or 1.5-35 mm² flexible, with a 3.5 N·m tightening torque and 15 mm strip length. Neutral position is left; toggle control with ON/OFF local indication.

Frequently asked questions

What is the breaking capacity of the A9N18346?

10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. It also carries 10 kA Icu at 220-240 V and 380-415 V AC under the industrial standard.

Where can I buy the A9N18346?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for the A9N18346?

The breaker is certified to EN/IEC 60898-1 and EN/IEC 60947-2, with tropicalisation class 2 per IEC 60068-1 and pollution degree 3 per IEC 60947-2. It is suitable for isolation per IEC 60947-2.