Schneider Electric A9N18382 — 2-Pole MCB (DIN Rail)

Schneider Electric A9N18382 Acti9 C120N MCB, D Curve, 63 A,

MPNA9N18382
Active

Schneider Electric Acti9 C120N, A9N18382, miniature circuit breaker, D curve, 63 A, 2 poles, 10 kA Icn at 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N18382 — Identification
ParameterValue
Product nameActi9 C120
Series / familyActi9
Device short nameC120N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N18382 — Electrical
ParameterValue
Rated current [In]63 A at 30 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N18382 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]7500 A 75 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Energy limitation class3 conforming to EN/IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N18382 — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N18382 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N18382 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1 EN/IEC 60947-2

Product details

The Schneider Electric A9N18382 is a 2-pole Acti9 C120N miniature circuit breaker with a D tripping curve, rated 63 A at 30 °C.

Rated at 10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. The D curve (10–14 x In magnetic trip) is sized for transformer inrush and motor-start loads — not general lighting or resistive circuits. The thermal-magnetic trip unit handles overloads on the bimetal side and short-circuits on the solenoid side.

Listed as current production. This is a standard-catalogue Acti9 C120N — no phase-out notice, no last-time-buy window.

Frequently asked questions

What is the breaking capacity of A9N18382?

10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. It also carries 10 kA Icu at 220–240 V AC and 20 kA Icu at 380–415 V AC under the 60947-2 standard.

What does the D curve mean on this breaker?

The D curve trips magnetically at 10–14 times the rated current. That suits loads with high inrush — transformers, motors, welding equipment — where a B or C curve would nuisance-trip on startup.

Where can I buy A9N18382 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.