Schneider Electric A9N18557 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N18557 Acti9 Vigi C120, 2P 125A RCD, Ty

MPNA9N18557
Active

Schneider Electric Acti9 Vigi C120, A9N18557, add-on residual current device, 2P, 125 A, Type A-SI, selective, 1000 mA, 230…415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N18557 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)1000 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
A9N18557 — Electrical Ratings
ParameterValue
Rated current (In)125 A
Rated operational voltage (Ue)230...415 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-1
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer Group incomer
Mechanical durability (operating cycles)20000 cycles
A9N18557 — Identification
ParameterValue
Product nameActi9 Vigi C120
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi C120
A9N18557 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width in 9 mm modules7
Terminal connectionsTunnel type terminals 1...35 mm² flexible Tunnel type terminals 1...50 mm² rigid
Wire stripping length15 mm
Terminal tightening torque3.5 N.m
Width117 mm
Height95 mm
Depth73 mm
A9N18557 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...60 °C
IP degree of protectionIP20
Pollution degree3 conforming to IEC 60947-2
A9N18557 — Approvals
ParameterValue
StandardsEN 61009 IEC/EN 61009-2-1

Product details

The Schneider Electric A9N18557 is an add-on residual current device (RCD) from the Acti9 Vigi C120 range, designed to clip onto the outgoing side of a compatible Acti9 MCB or switch-disconnector. It provides earth-leakage protection for the downstream circuit without requiring a separate enclosure or additional DIN-rail space — the unit mounts directly to the load-side terminals of the upstream device via the screw connection. Rated at 125 A on a 230…415 V AC 50 Hz network, this 2-pole device is intended for outgoer group incomer positions. The residual current protection class is Type A-SI (Super Immunised). Type A detects AC sinusoidal and pulsating DC fault currents; the SI suffix adds immunity to high-frequency leakage from variable-speed drives, UPS systems, or LED drivers that would otherwise cause nuisance tripping on a standard Type A device. This makes the A9N18557 a practical choice for commercial or light-industrial panels where non-linear loads are present.

The unit occupies 7 modules of 9 mm pitch, so the total width on the rail is 63 mm — the 117 mm overall width includes the overhang of the terminal housing. Depth is 73 mm, height 95 mm. Tunnel-type terminals accept 1…35 mm² flexible or 1…50 mm² rigid conductors. The rated impulse withstand voltage is 6 kV, and the rated insulation voltage is 500 V AC 50/60 Hz per IEC 60947-1.

Standards and lifecycle

These figures cover most indoor panel environments without derating, though the upper operating limit of 60 °C should be checked against the internal panel temperature rise if the device is mounted near high-current busbars or transformers.

Frequently asked questions

What is the A9N18557 used for?

It is an add-on residual current device (RCD) that clips onto the load side of a compatible Acti9 MCB or switch-disconnector to provide earth-leakage protection. With a 125 A rating, 1000 mA sensitivity, Type A-SI (Super Immunised) characteristic, and selective time delay, it is suited for main incoming or sub-main positions in distribution boards where coordination with downstream RCDs is required and where non-linear loads (VSDs, UPS, LED) are present.